Demand Overcurrent
DCTH Phase demand overcurrent element.
Pickup: 51PP < 4.0 A, secondary; 0.7 A to 60.2 A, secondary
51PP > 4.0 A, secondary; 0.2 A to 14.9 times 51PP setting, where 51PP
is the phase-time overcurrent element pickup setting. See Meter function
description.
Directional Elements
Phase directional element:
Angle: MTA (maximum torque angle) setting (47° - 90° in 1° steps).
Sensitivity: 1 VA of positive-sequence and 0.25 VA of negative-sequence at MTA
Memory: Eight cycles
Negative-sequence directional element:
Angle: MTA setting (47° - 90° in 1° steps).
Sensitivity: Proportional to 51P pickup for 4 A < 51PP < 12.6 A:
0.35 VA at 12.6 A pickup at MTA
0.11 VA at 4.0 A pickup and below at MTA
Zero-Sequence Directional Element
Current polarization:
Angle: 0°
Sensitivity: (0.5 A) x (51N pickup setting) at 0°, in units of residual amps squared,
and Ipol > 0.5 A.
Three-shot reclosing relay
79OI1 open interval 1,
79OI2 open interval 2,
79OI3 open interval 3:
Timer ranges: 0 - 10,000 cycles in quarter cycle steps. A setting of 0 disables that
shot and successive shots.
79RS reset interval:
Timer range: 60 - 8,000 cycles in quarter cycle steps
2-4
Specifications
SEL-267D/167D Instruction Manual
Date Code 920326
Summary of Contents for SEL-167D
Page 3: ......
Page 6: ......
Page 8: ......
Page 9: ......
Page 10: ......
Page 11: ......
Page 51: ...LOGIC DIAGRAMS Date Code 920326 Specifications SEL 267D 167D Instruction Manual 2 31 ...
Page 52: ...Date Code 920326 Specifications 2 32 SEL 267D 167D Instruction Manual ...
Page 53: ...Date Code 920326 Specifications SEL 267D 167D Instruction Manual 2 33 ...
Page 54: ...Date Code 920326 Specifications SEL 267D 167D Instruction Manual 2 34 ...
Page 88: ...SAMPLE EVENT REPORT ...
Page 114: ......
Page 115: ......