RECLOSING RELAY
The reclosing relay provides up to three shots of automatic reclosing for selectable fault types
and relay elements contained in the 32-bit Relay Word. The programmable logic provides
access to the internally derived reclose initiate and cancel signals. The relay also accepts
either external initiation or cancellation of reclosing. The three open intervals and the reset
timer are individually settable through the SET command.
To provide flexibility in applying the SEL-267D relay to various reclosing schemes, the
conditions for reclose initiation and cancellation are selected similarly to the output relay
programming:
RI
= R * MRI
MRI selects reclose initiate conditions from the Relay Word
RC = R * MRC
MRC selects reclose cancel conditions from the Relay Word
where MRI is the mask for reclose initiation, and MRC is the mask for reclose cancellation.
The open intervals do not begin until the TRIP output and 52A input deassert. Since the
TRIP output never asserts for less than the TDUR timer setting, the open interval may start
several milliseconds after the fault has actually cleared and the breaker opened.
Reclose is automatically cancelled when the circuit breaker is observed to trip with no fault
condition present or for faults during the open interval of any shot.
TARGETS
The front panel targets illuminate for the conditions are shown in the table below.
Table 2.6: Front Panel Target Conditions for Illumination
Target LED
Ø1
G1
Ø2
G2
Ø3
G3
51P
51N
Conditions for Illumination
Zone 1 phase involvement
Zone 1 ground involvement
Zone 2 phase involvement
Zone 2 ground involvement
Zone 3 phase involvement
Zone 3 ground involvement
Phase time-overcurrent involvement
Residual time-overcurrent involvement
Date Code 920326
Specifications
SEL-267D/167D Instruction Manual
2-17
Summary of Contents for SEL-167D
Page 3: ......
Page 6: ......
Page 8: ......
Page 9: ......
Page 10: ......
Page 11: ......
Page 51: ...LOGIC DIAGRAMS Date Code 920326 Specifications SEL 267D 167D Instruction Manual 2 31 ...
Page 52: ...Date Code 920326 Specifications 2 32 SEL 267D 167D Instruction Manual ...
Page 53: ...Date Code 920326 Specifications SEL 267D 167D Instruction Manual 2 33 ...
Page 54: ...Date Code 920326 Specifications SEL 267D 167D Instruction Manual 2 34 ...
Page 88: ...SAMPLE EVENT REPORT ...
Page 114: ......
Page 115: ......