EVENT REPORT
The SEL-267D relay records an eleven cycle event report following any of these elements
picking up:
67Nl
67Pl
51N
67N2
67P2
51P
67N3
67P3
Event reports are also recorded due to assertion of the following inputs and execution of the
following commands:
External Trigger input
Permissive Trip input
Direct Trip input
Block Trip input
OPEN command
TRIGGER command
A second report is triggered for the same fault if the trip occurs after the first report expires,
so the beginning and end of each fault for which the relay trips is recorded. A second event
report is not provided, however, if the TRIP output first asserts at or less than seven cycles
after the first report is triggered. (Note that reports are triggered at the 16th quarter cycle of
data.)
Timing of the triggering instant is recorded to the nearest quarter-cycle, so that the duration
of long faults can be computed from the time the first report is triggered by the fault, and the
time the second report is triggered by the trip. The reported event time corresponds to the
16th quarter cycle of the event report in all cases. The event report contains voltages,
currents, system settings, and other information. It is described in detail in the EVENT
REPORTING section.
Execution of the CLOSE command does not trigger an event. Direct close, by asserting the
DIRECT CLOSE input, does not trigger an event.
The twelve most recent event reports are stored in memory and may be retrieved using the
EVENT command. A short history of the twelve most recent events is available using the
HISTORY command.
FAULT LOCATOR
The SEL-267D relay fault locator is automatically triggered by any of several events. These
events include pickup of certain relay elements, assertion of certain contact inputs or outputs,
and user-entered commands. However, the fault locator can be either enabled or disabled
with the LOCAT setting in the setting procedure.
Date Code 920326
Specifications
SEL-267D/167D Instruction Manual
2-21
Summary of Contents for SEL-167D
Page 3: ......
Page 6: ......
Page 8: ......
Page 9: ......
Page 10: ......
Page 11: ......
Page 51: ...LOGIC DIAGRAMS Date Code 920326 Specifications SEL 267D 167D Instruction Manual 2 31 ...
Page 52: ...Date Code 920326 Specifications 2 32 SEL 267D 167D Instruction Manual ...
Page 53: ...Date Code 920326 Specifications SEL 267D 167D Instruction Manual 2 33 ...
Page 54: ...Date Code 920326 Specifications SEL 267D 167D Instruction Manual 2 34 ...
Page 88: ...SAMPLE EVENT REPORT ...
Page 114: ......
Page 115: ......