Table 3.1: Hexadecimal/Binary Conversion
Hexadecimal
Binary
Hexadecimal
Binary
0
1
2
3
4
5
6
7
0000
0001
0010
0011
0100
0101
0110
0111
8
9
A
B
C
D
E
F
1000
1001
1010
1011
1100
1101
1110
1111
For example, consider row 2 of mask MA1, which is set to 66 hex format. Using the table to
convert 66 to binary:
66 - > 0110 0110.
Now build row 2 of the Relay Word for mask MA1 as follows:
DFP
67N1
67N2
67N3
DFG
67P1
67P2
67P3
0
1
1
0
0
1
1
0
6
6
STATUS
The STATUS command allows inspection of the self test status. The relay also automatically
executes this command whenever a self test enters a warning or failure state, transmitting a
STATUS report to the port selected for automatic transmissions (see AUTO setting of the
SET procedure).
Date Code 920326
Commands and Serial Communication
SEL=267D/167D Instruction Manual
3-13