Date Code 980420
Operation Within SEL-2030
4-15
SEL-2711 Instruction Manual
*>>
SET P 18<ENTER>
SET P 18<ENTER>
Port communications settings for Port 18
Modbus Plus node Address (1-64)
ADDRESS = 12 ?
<ENTER>
<ENTER>
Map Input Registers to Holding Registers(Y/N)
MAP_IR = "N"
?
<ENTER>
<ENTER>
Control Point 1 routing path(Address range 1-247,0=OFF)
PATH_1 = "00.00.00.00.00"
?
2.5.0<ENTER>
2.5.0<ENTER>
Control Point 1 Modbus coil number
COIL_1 = 1 ? 36
Control Point 2 routing path(Address range 1-247,0=OFF)
PATH_2 = "00.00.00.00.00"
?
END<ENTER>
END<ENTER>
ADDRESS = 12
MAP_IR = "N"
PATH_1 = "2.5.0"
COIL_1 = 36
PATH_2 = "00.00.00.00.00"
COIL_2 = 1
PATH_3 = "00.00.00.00.00"
COIL_3 = 1
PATH_4 = "00.00.00.00.00"
COIL_4 = 1
PATH_5 = "00.00.00.00.00"
COIL_5 = 1
PATH_6 = "00.00.00.00.00"
COIL_6 = 1
PATH_7 = "00.00.00.00.00"
COIL_7 = 1
PATH_8 = "00.00.00.00.00"
COIL_8 = 1
PATH_9 = "00.00.00.00.00"
COIL_9 = 1
Press RETURN to continue
<ENTER>
<ENTER>
PATH_10 = "00.00.00.00.00"
COIL_10 = 1
PATH_11 = "00.00.00.00.00"
COIL_11 = 1
PATH_12 = "00.00.00.00.00"
COIL_12 = 1
PATH_13 = "00.00.00.00.00"
COIL_13 = 1
PATH_14 = "00.00.00.00.00"
COIL_14 = 1
PATH_15 = "00.00.00.00.00"
COIL_15 = 1
PATH_16 = "00.00.00.00.00"
COIL_16 = 1
Save changes (Y/N) ?
Y<ENTER>
Y<ENTER>
Settings accepted.
*>>
(continued on next page)