4-30
Operation Within SEL-2030
Date Code 980420
SEL-2711 Instruction Manual
Table 4.14: Relay History Record Holding Register Map
Relative
Address
Description
0
Month
1
Day
2
Year
3
Hour
4
Minute
5
Second
6
Millisecond
7
Event - see
Event Type
subsection below
8
Distance/location - whole part
9
Distance/location - fractional part multiplied by 10000
10
Shot
11
52 A in cycles/100
12
Group
13
Target - see
Target Type
subsection below
14
Duration - whole part in seconds; for 50 Hz relays, must multiply this
value by 6/5 to get seconds
15
Duration - fractional part in seconds/10000
16
Fault current - whole part in amps
17
Fault current - fractional part in amps/10000
18
IV Time in cycles/100
19
Energy in MJ/10