Date Code 980420
Operation Within SEL-2030
4-3
SEL-2711 Instruction Manual
that you may press any key to initiate the firmware download. Press a key and then send the
new SEL-2711 SEL
BOOT
code using an XMODEM file transfer.
If you are upgrading the SEL-2030 SEL
BOOT
code:
Type the command “REC boot”. Respond “Y” to the confirmation prompt. Once the
SEL-2030 is ready to receive the new code, it will display another prompt indicating that you
may press any key to initiate the firmware download. Press a key and then send the new
SEL-2030 SEL
BOOT
code using an XMODEM file transfer.
6.
Once the transfer is complete, the SEL-2030 will indicate whether or not the new code was
successfully received. If the transfer was not successful, repeat step 5. Once the transfer
succeeds, repeat step 5 if you are upgrading multiple programs and/or multiple protocol cards.
Once you have completed all upgrades, enter the command “EXI” to return the SEL-2030 and
its protocol cards to normal operation.
7.
In order to communicate with the SEL-2030, you will need to change the baud rate on your
communications software back to the value that is set in your SEL-2030 Front panel port
settings. This should be the same baud rate as was used in establishing communications in
step 1.
C
ONFIGURING
SEL-2711
There are a number of settings associated with the SEL-2711. To access these settings, use the
SET P 17 or SET P 18 command in the SEL-2030. (The SEL-2711 is installed as Port 17 or 18 in
the SEL-2030; examine the rear panel or use the STATUS command to determine which slot it is
in.) The following screen capture shows what the setting process looks like:
*>>
SET P 17<ENTER>
SET P 17<ENTER>
Port communications settings for Port 17
Modbus Plus node Address (1-64)
ADDRESS = 1 ?
17<ENTER>
17<ENTER>
Map Input Registers to Holding Registers(Y/N)
MAP_IR = "N"
?
<ENTER>
<ENTER>
Control Point 1 routing path(Address range 1-247,0=OFF)
PATH_1 = "00.00.00.00.00"
?
<ENTER>
<ENTER>
Control Point 1 Modbus coil number
COIL_1 = 1 ?
<ENTER>
<ENTER>
Control Point 2 routing path(Address range 1-247,0=OFF)
PATH_2 = "00.00.00.00.00"
?
END<ENTER>
END<ENTER>
ADDRESS = 17
MAP_IR = "N"
PATH_1 = "00.00.00.00.00"
COIL_1 = 1
PATH_2 = "00.00.00.00.00"
COIL_2 = 1
PATH_3 = "00.00.00.00.00"
COIL_3 = 1
PATH_4 = "00.00.00.00.00"
COIL_4 = 1
(continued on next page)