SEL-2711 Instruction Manual
Meter Data
The meter data differs significantly between relays. Therefore, the data stored in a specific register
depends on the data available from the attached relay. All meter data is primary quantities, unless
otherwise indicated. Table 4.8 lists the possible quantities for each register.
Some quantities have the whole and fractional parts separated into two registers. In these cases,
the second register contains the fractional part multiplied by 10000. For example, a power of
73.1274 MW would be reported as 73 in register 44 and 1274 in register 45. Similarly, a reactive
power of -8.2390 MVAR would be reported as -8 in register 46 and -2390 in register 47.
For this data to be available, the SEL-2030 must be set to perform 20METER collection with the
attached relay.
Table 4.8: Relay Meter Data Holding Register Map
Relative
Address
Description
40
IA, IAX, IAW1, or IA1 in amps; or dVA or dV12 in secondary V/100
41
IB, IBX, IBW1, or IB1 in amps; or dVB or dV34 in secondary V/100
42
IC, ICX, ICW1, or IC1 in amps; or dVC or dV56 in secondary V/100
43
IR, I0, I0_1, or IRX in amps
44
P or P1 whole part in MW
45
P or P1 fractional part in MW/10000
46
Q or Q1 whole part in MVAR
47
Q or Q1 fractional part in MVAR/10000
48
3I2, I2 as 3I2, 3I2X, or I2_1 as 3I2_1 in amps
49
VA or VA1 in kV/10; or V1 or VAX in secondary V/100; or IAY, IAW2,
or IA2 in amps
50
VB or VB1 in kV/10; or V3 or VBX in secondary V/100; or IBY, IBW2,
or IB2 in amps
51
VC or VC1 in kV/10; or V5 or VCX in secondary V/100; or ICY, ICW2,
or IC2 in amps
52
3V0, V0 as 3V0, or V0_1 as 3V0_1 in kV/10; VPL in secondary V/100;
or IRY or I0_2 in amps
53
VAB or VAB1 in kV/10; V2 or VAY in secondary V/100; or IABY or
IAB2 in amps
54
VBC or VBC1 in kV/10; V4 or VBY in secondary V/100; or IBCY or
IBC2 in amps
55
VCA or VCA1 in kV/10; V6 or VCY in secondary V/100; or ICAY or
ICA2 in amps