Date Code 981030
Operation Within SEL-2030
4-39
SEL-2711 Instruction Manual
Relative
Address
Description
Units
Range
272
1
st
event group number
1-6
273
1
st
event targets
TBD
274-279
Unused - always 8000h
280
2
nd
event month
months
1-12
.
.
.
.
.
.
.
.
.
.
.
.
493
12
th
event targets
TBD
494-499
Unused - always 8000h
SEL-351
Relative
Address
Description
Units
Range
0
Relay Type - 35100
0-65535
1-39
Reserved - always 8000h
40
Phase A current (IA)
amps, primary
0-32767 A
41
Phase B current (IB)
amps, primary
0-32767 A
42
Phase C current (IC)
amps, primary
0-32767 A
43
Zero-sequence current (I0)
amps, primary
0-32767 A
44
Power, whole part (P)
MW, primary
-32767-32767 MW
45
Power, fractional part (P)
MW/10000, primary
-0.9999-0.9999 MW
46
Reactive power, whole part (Q)
MVAR, primary
-32767-32767 MVAR
47
Reactive power, fractional part (Q)
MVAR/10000, primary
-0.9999-0.9999 MVAR
48
Negative-sequence current (3I2)
amps, primary
0-32767 A
49
Phase A voltage (VA)
kV/10, primary
0.0-3276.7 kV
50
Phase B voltage (VB)
kV/10, primary
0.0-3276.7 kV
51
Phase C voltage (VC)
kV/10, primary
0.0-3276.7 kV
52
Zero-sequence voltage (3V0)
kV/10, primary
0.0-3276.7 kV
53
AB differential voltage (VAB)
kV/10, primary
0.0-3276.7 kV
54
BC differential voltage (VBC)
kV/10, primary
0.0-3276.7 kV
55
CA differential voltage (VCA)
kV/10, primary
0.0-3276.7 kV
56
Negative-sequence voltage (3V2)
kV/10, primary
0.0-3276.7 kV
57
AB difference current (IAB)
amps, primary
0-32767 A
58
BC difference current (IBC)
amps, primary
0-32767 A
59
CA difference current (ICA)
amps, primary
0-32767 A
60
Phase A demand current (IA)
amps, primary
0-32767 A
61
Phase B demand current (IB)
amps, primary
0-32767 A
62
Phase C demand current (IC)
amps, primary
0-32767 A
63-67
Unused - always 8000h
68
Negative-sequence demand current (3I2)
amps, primary
0-32767 A
69-79
Unused, always 8000h
80
Month of last meter data acquisition
months
1-12
81
Day of last meter data acquisition
days
1-31
82
Year of last meter data acquisition
years
1900-2100
83
Hour of last meter data acquisition
hours
0-23
84
Minute of last meter data acquisition
minutes
0-59
85
Second of last meter data acquisition
seconds
0-59
86-159
Reserved - always 8000h
160
Status byte and relay word row 0
161
Relay word rows 1 and 2
.
.
.
.
.
.
183
Relay word rows 45 and 46
184-209
Reserved - always 8000h
210
Month of most recent event
months
1-12
211
Day of month of most recent event
days
1-31
212
Year of most recent event
years
1900-2100
213
Hour of most recent event
hours
0-23
214
Minute of most recent event
minutes
0-59
215
Second of most recent event
seconds
0-59
216
Millisecond of most recent event
milliseconds
0-999
217-219
Unused - always 8000h
220
Event type
TBD
TBD
221
Shot