Date Code 981030
Operation Within SEL-2030
4-41
SEL-2711 Instruction Manual
Relative
Address
Description
Units
Range
63
Residual, X side demand current (IRX)
amps, primary
0-32767 A
64
Phase A, Y side demand current (IAY)
amps, primary
0-32767 A
65
Phase B, Y side demand current (IBY)
amps, primary
0-32767 A
66
Phase C, Y side demand current (ICY)
amps, primary
0-32767 A
67
Residual, Y side demand current (IRY)
amps, primary
0-32767 A
68
Negative-sequence, X side demand current (3I2X)
amps, primary
0-32767 A
69
Negative-sequence, X side demand current (3I2X)
amps, primary
0-32767 A
70-79
Unused, always 8000h
80
Month of last meter data acquisition
months
1-12
81
Day of last meter data acquisition
days
1-31
82
Year of last meter data acquisition
years
1900-2100
83
Hour of last meter data acquisition
hours
0-23
84
Minute of last meter data acquisition
minutes
0-59
85
Second of last meter data acquisition
seconds
0-59
86-159
Reserved - always 8000h
160
Status register and X Relay word row 0
161
X Relay word rows 1 and 2
162
X Relay word row 3 and Y Relay word row 0
163
Y Relay word rows 1 and 2
164
Y Relay word row 3 and I/O status register
165-209
Reserved - always 8000h
210
Month of most recent event
months
1-12
211
Day of month of most recent event
days
1-31
212
Year of most recent event
years
1900-2100
213
Hour of most recent event
hours
0-23
214
Minute of most recent event
minutes
0-59
215
Second of most recent event
seconds
0-59
216
Millisecond of most recent event
milliseconds
0-999
217-219
Unused - always 8000h
220
Event type
TBD
TBD
221-223
Unused - always 8000h
224
Fault targets of most recent fault
TBD
225-239
Unused - always 8000h
240-259
Reserved - always 8000h
260
1
st
event month
months
1-12
261
1
st
event day of month
days
1-31
262
1
st
event year
years
1900-2100
263
1
st
event hour
hours
0-23
264
1
st
event minute
minutes
0-59
265
1
st
event second
seconds
0-59
266
1
st
event millisecond
milliseconds
0-999
267
1
st
event type
TBD
268-272
Unused - always 8000h
273
1
st
event targets
TBD
274-279
Unused - always 8000h
280
2
nd
event month
months
1-12
.
.
.
.
.
.
.
.
.
.
.
.
493
12
th
event targets
494-499
Unused - always 8000h
SEL-BFR
Relative
Address
Description
Units
Range
0
Relay Type - 7
0-65535
1-39
Reserved - always 8000h
40
Phase A current (IA)
amps, primary
0-32767 A
41
Phase B current (IB)
amps, primary
0-32767 A
42
Phase C current (IC)
amps, primary
0-32767 A
43
Unused - always 8000h
44
Power, whole part (P)
MW, primary
-32767-32767 MW
45
Power, fractional part (P)
MW/10000, primary
-0.9999-0.9999 MW
46
Reactive power, whole part (Q)
MVAR, primary
-32767-32767 MVAR
47
Reactive power, fractional part (Q)
MVAR/10000, primary
-0.9999-0.9999 MVAR