1-16
Introduction and Specifications
Date Code 20060731
SEL-300G Instruction Manual
Supervisory Slip
Frequency Window
Element:
–1.00 Hz–1.00 Hz
Steady-State Slip
Accuracy:
± 0.02 Hz
Close Acceptance
Angle 1, 2:
0–80°
Target Close Angle:
–15–15°
Breaker Close Delay:
0.000–1.000 s
Close Failure Angle:
3–120°
Steady-State Angle
Accuracy:
± 0.5°
Maximum Transient
Angle Accuracy:
± 1.8 • slip ± 0.5°
Directional Power Element (32):
Two Definite-Time Elements
Setting Range:
± 0.0015 to ± 3.000 pu
Steady-State
Pickup Accuracy:
± 0.0015 pu ± 2% of setting,
INOM = 5 A, VNOM = 120 V,
PF
≥
0.2
Pickup Time:
25 ms at 60 Hz (Max)
Definite-Time Setting
Range:
0.01–400.00 s
Maximum Definite-Time
Delay Accuracy:
± 0.1%, ± 4.2 ms at 60 Hz
Loss-of-Field Element (40):
Two Mho Zones
5 A
Model
Zone 1 Offset:
–50.0–0.0 ohms
Zone 2 Offset:
–50.0–50.0 ohms
Zone 1 and Zone 2
Diameter:
0.1–100.0 ohms
Steady-State
Impedance Accuracy:
± 0.1 ohm, ± 5% of
diameter
Minimum
Pos.-Seq. Signals:
0.25 V V1, 0.25 A I1
1 A Model
Zone 1 Offset:
–250.0–0.0 ohms
Zone 2 Offset:
–250.0–250.0 ohms
Zone 1 and Zone 2
Diameter:
0.5–500.0 ohms
Steady-State
Impedance Accuracy:
± 0.5 ohm, ± 5% of
diameter
Minimum Pos.-Seq.
Signals:
0.25 V V1, 0.05 A I1
Directional Element
Angle:
–20.0
°
–0.0
°
Pickup Time:
50 ms at 60 Hz (Max)
Zone 1 and Zone 2
Definite-Time Delays:
0.00–400.00 s
Maximum Definite-Time
Delay Accuracy:
± 0.1%, ± 8.3 ms at 60 Hz
Negative-Sequence Overcurrent Elements (46):
Definite-Time and
Inverse-Time
Neg.-Seq. I
2
Pickup:
2%–100% of generator rated
secondary current
Generator Rated
Secondary Current:
5 A Model: 2.5–10.0 A secondary
1 A Model: 0.5–2.0 A secondary
Steady-State
Pickup Accuracy:
5 A Model: ± 0.025 A, ± 3%
1 A Model: ± 0.005 A, ± 3%
Pickup Time:
50 ms at 60 Hz (Max)
Definite-Time Delay
Setting Range:
0.02–999.90 s
Maximum Definite-Time
Delay Accuracy:
± 0.1%, ± 4.2 ms at 60 Hz
Inverse-Time Element
Time Dial:
K = 1 to 100 s
Linear Reset Time:
240 s fixed
Inverse-Time Timing
Accuracy:
± 4%, ± 50 ms at 60 Hz for |I
2
|
above 1.05 multiples of pickup
Instantaneous/Definite-Time Overcurrent
Elements (50):
Phase, Residual Ground, Neutral Protection
Current Pickup
(A secondary):
5 A Model: 0.25–100.00
1 A Model: 0.05–20.00
Steady-State
Pickup Accuracy:
5 A Model: ± 0.05 A, ± 3%
1 A Model: ± 0.01 A, ± 3%
Transient Overreach:
± 5% of pickup
Pickup Time:
25 ms at 60 Hz (Max)
Note:
50 ms for 50Q element.
Time Delay:
0.00–400.00 s
Timer Accuracy:
± 0.1%, ± 4.2 ms at 60 Hz
Inverse Time-Overcurrent Elements (51):
Residual Ground and Neutral Protection
Current Pickup
(A secondary):
5 A Model: 0.5–16.0
1 A Model: 0.1–3.2 A
Steady-State Pickup
Accuracy:
5 A Model: ± 0.05 A, ± 3%
1 A Model: ± 0.01 A, ± 3%
Time Dials:
US: 0.5–15.0, 0.01 steps
IEC: 0.05–1.00, 0.01 steps
Timing:
± 4%, ± 25 ms at 60 Hz for |I|
between 2 and 20 multiples of
pickup
Voltage Restrained Phase Time-Overcurrent
Element (51V):
Phase Pickup
(A secondary):
5 A Model: 2.0–16.0
1 A Model: 0.4–3.2
Steady-State
Pickup Accuracy:
5 A Model: ± 0.05 A, ± 3%
1 A Model: ± 0.01 A, ± 3%
US: 0.5–15.0, 0.01 steps
Time Dials:
IEC: 0.05–1.00, 0.01 steps
Timing
:
± 4%, ± 25 ms at 60 Hz for |I|
between 2 and 20 multiples of
pickup
Voltage Restraint Type: Linear restraint
Voltage Controlled Phase Time-Overcurrent
Element (51C):
Phase Pickup
(A secondary):
5 A Model: 0.5–16.0
1 A Model: 0.1–3.2
Steady State
Pickup Accuracy:
5 A Model: ± 0.05 A, ± 3%
1 A Model: ± 0.01 A, ± 3%
Time Dials:
US: 0.5–15.0, 0.01 steps
IEC: 0.05–1.00, 0.01 steps
Timing:
± 4%, ± 25 ms for |I| between 2 and
20 multiples of pickup
Summary of Contents for SEL-300G
Page 1: ...SEL 300G Multifunction Generator Relay Instruction Manual 20060731 PM300G 01 NB ...
Page 4: ......
Page 6: ......
Page 138: ......
Page 166: ......
Page 170: ......
Page 288: ......
Page 290: ......
Page 328: ......
Page 442: ......
Page 456: ......
Page 458: ......
Page 468: ......
Page 470: ......
Page 512: ......
Page 516: ......
Page 518: ......
Page 552: ......
Page 554: ......
Page 560: ......
Page 578: ......
Page 626: ......
Page 724: ......
Page 728: ......