Enter Relay Settings
6-7
SEL-300G Instruction Manual
Date Code 20060731
When you press the front-panel SET button, the front-panel LCD displays the following options:
GROUP GLOBAL
PORT PASS
The underlined G in GROUP identifies that, if you press the SELECT pushbutton, you will be
presented with options associated with the relay element group settings. Move the underline to
select the other options by pressing the Up, Down, Left, and Right arrow pushbuttons. Figure 6.1
summarizes the SET pushbutton options.
To terminate settings viewing or modification at any point in the process, press the EXIT
pushbutton. The relay will return to the default display without saving any setting modifications.
Within the settings lists, the relay displays the setting category name. Press the SELECT
pushbutton to view or modify settings within that category. Use the Up and Down arrow
pushbuttons to maneuver within the settings list.
After finding the setting you wish to modify, press the SELECT pushbutton.
Modify numeric settings by using the Left, Right arrow pushbuttons to underline single digits,
then the Up, Down arrow pushbuttons to change the digit, similar to moving a thumbwheel.
Modify Y/N enable settings by using the Up, Down arrow pushbuttons to change the setting from
Y to N and back.
To learn more about a setting and its range, press the Target Reset/Lamp Test pushbutton while
the setting is displayed.
After modifying a setting, press the SELECT pushbutton to proceed to the next setting.
After finishing all setting modifications, press the Down arrow pushbutton several times to
proceed to the bottom of the settings list. The relay will display the message:
Save Changes
ÅÆ
Yes No
To save your modifications and enable the relay with your new settings, press the SELECT
pushbutton with underscore beneath the Y in Yes.
To exit without saving, press the Right arrow pushbutton to move the underscore beneath the N
in No, then press the SELECT pushbutton.
Summary of Contents for SEL-300G
Page 1: ...SEL 300G Multifunction Generator Relay Instruction Manual 20060731 PM300G 01 NB ...
Page 4: ......
Page 6: ......
Page 138: ......
Page 166: ......
Page 170: ......
Page 288: ......
Page 290: ......
Page 328: ......
Page 442: ......
Page 456: ......
Page 458: ......
Page 468: ......
Page 470: ......
Page 512: ......
Page 516: ......
Page 518: ......
Page 552: ......
Page 554: ......
Page 560: ......
Page 578: ......
Page 626: ......
Page 724: ......
Page 728: ......