7-18 Relay
Commissioning
Date Code 20060731
SEL-300G Instruction Manual
Table 7.4: Serial Port Commands That Clear Relay Data Buffers
Serial Port
Command
Task Performed:
MET RD
Resets Demand Meter Data
MET RP
Resets Peak Demand Meter Data
MET RE
Resets Energy Meter Data
MET RM
Resets Max/Min Data
HIS C
Clears Event Report and History Command Buffers
PRO R
Resets Selected Generator Operating Statistic Buffers
SER C
Clears Sequential Events Record Buffer
Note:
The
PRO R
and
SER C
commands should only be used at initial installation.
Do not reset the generator operating profiles or SER buffer following routine
maintenance unless you are very familiar with the use of the data contained in
these buffers.
Step 23.
Set the Breaker Monitor function SEL
OGIC
control equation enable BKMON back to
the setting specified by your Settings Sheets. If desired, use the
SHO 1
,
SHO 2
,
SHO G
, and
SHO R
commands to record the relay settings. The relay is now ready
for operation.
P
ROTECTION
E
LEMENT
T
ESTS
Introduction
This section describes detailed test procedures for individual protection elements. While it is not
necessary to test every protection function provided by the relay at commissioning time, you may
wish to test selected elements to verify correct element operation.
Note:
Many of the protection functions include torque-control settings, as described in
Section 2: Relay Element Settings
. To test these elements, either set the torque-control
setting directly to logical 1 or ensure that the torque-controlling conditions are satisfied
by the test signals. If an element under test does not respond to test signals, verify that
the torque-control condition is asserted before proceeding with further troubleshooting.
Three Voltage Source and Three Current Source Connections
Figure 7.9 shows connections to use when three voltage sources and three current sources are
available. Figure 7.10 shows connections to use when two voltage sources and three current
sources are available.
Summary of Contents for SEL-300G
Page 1: ...SEL 300G Multifunction Generator Relay Instruction Manual 20060731 PM300G 01 NB ...
Page 4: ......
Page 6: ......
Page 138: ......
Page 166: ......
Page 170: ......
Page 288: ......
Page 290: ......
Page 328: ......
Page 442: ......
Page 456: ......
Page 458: ......
Page 468: ......
Page 470: ......
Page 512: ......
Page 516: ......
Page 518: ......
Page 552: ......
Page 554: ......
Page 560: ......
Page 578: ......
Page 626: ......
Page 724: ......
Page 728: ......