7-66 Relay
Commissioning
Date Code 20060731
SEL-300G Instruction Manual
t
(seconds)
46
Q2P
Test 1
Test 2
Test 3
I2
(percent of INOM)
DWG: M300G112
Actual tripping time defined
by 46Q2K settings
25
50
100
Figure 7.21: 46Q2 Inverse-Time Element Test
Step 1.
Use the equations below to calculate the test current magnitudes for Test Point 1, Test
Point 2, and Test Point 3.
INOM
25
.
0
3
1
Itest
⋅
⋅
=
A secondary
Itest1 = ___________ A secondary
INOM
5
.
0
3
2
Itest
⋅
⋅
=
A secondary
Itest2 = ___________ A secondary
INOM
0
.
1
3
3
Itest
⋅
⋅
=
A secondary
Itest3 = ___________ A secondary
Calculate the expected operate time at each test point using the equation:
2
INOM
3
Itestn
K
2
Q
46
Topn
⎟
⎠
⎞
⎜
⎝
⎛
⋅
=
seconds
Top1 = _____________ seconds
Top2 = _____________ seconds
Top3 = _____________ seconds
Step 2.
Based on the two timing test descriptions above (SER or output contact driving an
external timer), select one method and make the settings and connections necessary to
support the selection. Configure the current test source to apply single-phase current
with a magnitude equal to Itest1.
Summary of Contents for SEL-300G
Page 1: ...SEL 300G Multifunction Generator Relay Instruction Manual 20060731 PM300G 01 NB ...
Page 4: ......
Page 6: ......
Page 138: ......
Page 166: ......
Page 170: ......
Page 288: ......
Page 290: ......
Page 328: ......
Page 442: ......
Page 456: ......
Page 458: ......
Page 468: ......
Page 470: ......
Page 512: ......
Page 516: ......
Page 518: ......
Page 552: ......
Page 554: ......
Page 560: ......
Page 578: ......
Page 626: ......
Page 724: ......
Page 728: ......