10-30
Serial Port Communications and Commands
Date Code 20060731
SEL-300G Instruction Manual
COMM MODULE
Description
FAIL N/A
Lost
communications.
FAIL
FAIL
Lost communications, but last communication from
device contained a status word indicating a remote
failure.
The relay latches all self-test warnings and failures in order to capture transient out-of-tolerance
conditions.
Refer to Table 4.5 in
Section 4: SEL
OGIC
Control Equations
for self-test thresholds and
corrective actions.
SYN Command (Synch-Check Function Report) (Models 0300G2 and 0300G3)
The
SYN
command displays the latest of three reports stored by the relay synch-check function in
nonvolatile memory. For more information on SYN reports, see
Section 11: Event Reports and
SER Functions
.
TAR Command (Display Relay Element Status)
The
TAR
command displays the status of front-panel target LEDs or relay elements, whether
they are asserted or deasserted. The elements are represented as Relay Word bits and are listed in
rows of eight, called Relay Word rows. For additional information on individual Relay Word
bits, refer to
Section 4: SEL
OGIC
Control Equations
.
A Relay Word bit is either at a logical 1 (asserted) or a logical 0 (deasserted). Relay Word bits
are used in SEL
OGIC
control equations. See
Section 6: Enter Relay Settings
and
Section 4:
SEL
OGIC
Control Equations
.
The serial port
TAR
command does not remap the front-panel target LEDs. But the execution of
the equivalent
TAR
command via the front-panel display does remap the bottom row of the front-
panel target LEDs (see Figure 9.3, pushbutton <OTHER>).
The
TAR
command options are:
TAR
n k
Shows Relay Word row number
n
(0–43).
k
is an optional parameter to
specify the number of times (1–32767) to repeat the Relay Word row
display. If
k
is not specified, the Relay Word row is displayed once.
TAR name
k
Shows Relay Word row containing Relay Word bit name (e.g.,
TAR 40Z1
displays Relay Word Row 5). Valid names are shown in Table 10.7.
k
is an
optional parameter to specify the number of times (1–32767) to repeat the
Relay Word row display. If
k
is not specified, the Relay Word row is
displayed once.
Summary of Contents for SEL-300G
Page 1: ...SEL 300G Multifunction Generator Relay Instruction Manual 20060731 PM300G 01 NB ...
Page 4: ......
Page 6: ......
Page 138: ......
Page 166: ......
Page 170: ......
Page 288: ......
Page 290: ......
Page 328: ......
Page 442: ......
Page 456: ......
Page 458: ......
Page 468: ......
Page 470: ......
Page 512: ......
Page 516: ......
Page 518: ......
Page 552: ......
Page 554: ......
Page 560: ......
Page 578: ......
Page 626: ......
Page 724: ......
Page 728: ......