Event Reports and SER Functions
11-1
SEL-300G Instruction Manual
Date Code 20060731
SECTION 11: EVENT REPORTS AND SER FUNCTIONS
I
NTRODUCTION
The SEL-300G Relay offers two styles of event reports:
•
Standard 15-, 30-, 60-, 180-cycle event reports
•
Sequential Events Recorder (SER) report
Resolution: 1
ms
Accuracy: +1/4
cycle
These event reports contain date, time, current, voltage, frequency, relay element, optoisolated
input, and output contact information. Event reports generated by SEL-300G_1 Relays also
include data describing the operation of the differential measurements and elements.
The relay generates (triggers) standard 15-, 30-, 60-, or 180-cycle event reports by fixed and
programmable conditions. These reports show information for 15, 30, 60, or 180 continuous
cycles. The relay stores the event report data in nonvolatile memory. Up to twenty-nine
15-cycle, fifteen 30-cycle, eight 60-cycle, or two 180-cycle reports are maintained; if more
reports are triggered, the latest event report overwrites the oldest event report. See Figure 11.2
for an example standard 15-cycle event report.
The relay adds lines in the SER report for a change of state of a programmable condition. The
SER lists date and time-stamped lines of information each time a programmed condition changes
state. The relay stores the latest 512 lines of the SER report in nonvolatile memory. If the report
fills up, newer rows overwrite the oldest rows in the report. See Figure 11.6 for an example SER
report.
Relays equipped with synchronism checking also generate reports showing relay and breaker
performance during synch-check supervised closes.
S
TANDARD
E
VENT
R
EPORTS
See Figure 11.2 for an example event report (
Note
: Figure 11.2 is on multiple pages).
Event Report Length (Settings LER and PRE)
The SEL-300G provides user-programmable event report length and prefault length. Event
report length is 15, 30, 60, or 180 cycles. Prefault length ranges from 1 to LER-1 cycles.
Prefault length is the first part of the event report that precedes the event report triggering point.
Set the event report length with the LER setting. Set the prefault length with the PRE setting.
Changing the LER setting will erase all events stored in nonvolatile memory. Changing the PRE
setting has no effect on the nonvolatile reports.
Summary of Contents for SEL-300G
Page 1: ...SEL 300G Multifunction Generator Relay Instruction Manual 20060731 PM300G 01 NB ...
Page 4: ......
Page 6: ......
Page 138: ......
Page 166: ......
Page 170: ......
Page 288: ......
Page 290: ......
Page 328: ......
Page 442: ......
Page 456: ......
Page 458: ......
Page 468: ......
Page 470: ......
Page 512: ......
Page 516: ......
Page 518: ......
Page 552: ......
Page 554: ......
Page 560: ......
Page 578: ......
Page 626: ......
Page 724: ......
Page 728: ......