2-34
Relay Element Settings
Date Code 20060731
SEL-300G Instruction Manual
Setting Descriptions
Enable Loss-of-Field Protection (Y, N)
E40 = Y
Set E40 = Y to enable loss-of-field protection elements. If loss-of-field protection is
not required, set E40 = N. When E40 = N, the 40ZTC, 40Z1, 40Z1T, 40Z2, and 40Z2T
Relay Word bits are inactive and the relay does not require that the following settings
be entered.
Zone 1 Mho Diameter (OFF, 0.1–100.0
Ω
, 5 A relay)
40Z1P = 13.4
(OFF, 0.5–500.0
Ω
, 1 A relay)
Zone 1 Offset Reactance (–50.0–0.0
Ω
, 5 A relay)
40XD1 = –2.5
(–250.0–0.0
Ω
, 1 A relay)
Zone 1 Pickup Time Delay (0.00–400.00 s)
40Z1D = 0.00
The Zone 1 element typically is applied as a tripping function. Zone 1 diameter and
offset setting guidelines are described below. Set the Zone 1 offset equal to one-half
the generator transient reactance,
d
X
′
, in secondary ohms. Zone 1 loss-of-field tripping
is typically performed with short or zero time delay. Any desired delay should be
added using the 40Z1D setting.
The 40Z1 Relay Word bit asserts without time delay when the measured positive-
sequence impedance falls within the Zone 1 mho circle defined by the offset and
diameter settings. The 40Z1D Relay Word bit asserts 40Z1D seconds after 40Z1
asserts.
Zone 2 Mho Diameter (OFF, 0.1–100.0
Ω
, 5 A relay)
40Z2P = 13.4
(OFF, 0.5–500.0
Ω
, 1 A relay)
Zone 2 Offset Reactance (–50.0–50.0
Ω
, 5 A relay)
40XD2 = –2.5
(–250.0–250.0
Ω
, 1 A relay)
Zone 2 Pickup Time Delay (0.00–400.00 s)
40Z2D = 0.50
Zone 2 Directional Superv. Angle (–20.0
°
–0.0
°
)
40DIR = –10.0
The Zone 2 element typically is applied as a time-delayed tripping function. Zone 2
diameter and offset setting guidelines are described below.
Zone 2 loss-of-field tripping typically is performed with 0.5 to 0.6 second time delay.
Set 40Z2D equal to the desired delay.
The 40DIR setting is hidden when 40XD2 < 0.
The 40Z2 Relay Word bit asserts without time delay when the measured positive
sequence impedance falls within the Zone 2 mho circle defined by the offset and
diameter settings, and below the directional supervision line, if used. The 40Z2T Relay
Word bit asserts 40Z2D seconds after 40Z2 asserts.
40Z Element Torque Control (SEL
OGIC
control equation):
40ZTC = !60LOP
Summary of Contents for SEL-300G
Page 1: ...SEL 300G Multifunction Generator Relay Instruction Manual 20060731 PM300G 01 NB ...
Page 4: ......
Page 6: ......
Page 138: ......
Page 166: ......
Page 170: ......
Page 288: ......
Page 290: ......
Page 328: ......
Page 442: ......
Page 456: ......
Page 458: ......
Page 468: ......
Page 470: ......
Page 512: ......
Page 516: ......
Page 518: ......
Page 552: ......
Page 554: ......
Page 560: ......
Page 578: ......
Page 626: ......
Page 724: ......
Page 728: ......