F-10
Modbus RTU Communications Protocol
Date Code 20060731
SEL-300G Instruction Manual
The relay responses to errors in the query are shown below:
Error
Error Code
Returned
Communication
Counter Increments
Illegal
register to read
Illegal Data Address
(02h)
Invalid Address
Illegal number of
registers to read
Illegal Data Value
(03h)
Illegal Register
Format error
Illegal Data Value
(03h)
Bad Packet Format
Busy
Slave is busy with
other task (06h)
05h Force Single Coil Command
Use function code 05h to set or clear a coil.
Table F.10: 05h Force Single Coil Command
Bytes Field
Requests from the master must have the following format:
1 byte
Slave Address
1 byte
Function Code (05h)
2 bytes
Coil Reference
1 byte
Operation Code (FF for bit set, 00 for bit clear)
1 byte
Placeholder (00)
2 bytes
CRC-16
Note: The command response is identical to the command request.