4-20 SEL
OGIC
Control Equations
Date Code
20060731
SEL-300G Instruction Manual
C
LOSE
L
OGIC
The close logic in Figure 4.8 provides flexible circuit breaker closing with SEL
OGIC
control
equation settings:
52A (breaker
status)
CLEN (CLOSE
enable)
CL
(close conditions, other than
CLOSE
command)
ULCL
(unlatch close conditions, other than circuit breaker status)
ULCL
CLOSE
Serial
Port
Command
CL
CLOSE
52A
CLEN
SEL
OGIC
Setting
0
CLSD
DWG: M300G066
SEL
OGIC
Setting
Reset
Timer
Figure 4.8: Close Logic
Set Close
If
all
the following are true:
•
The unlatch close condition is not asserted (ULCL = logical 0)
•
The circuit breaker is open (52A = logical 0)
•
Closing is enabled (CLEN = logical 1)
Then the CLOSE Relay Word bit can be asserted to logical 1 if any
one
of the following occurs:
•
The serial communications port
CLOSE
command is executed
•
SEL
OGIC
control equation setting CL goes from logical 0 to logical 1 (rising edge
transition)
If a serial port
CLOSE
command is executed or CL goes from logical 0 to logical 1 while the
CLEN SEL
OGIC
control equation is logical 0, the relay waits for CLSD close dwell time seconds
for CLEN to assert. If CLEN asserts before CLSD expires, the CLOSE Relay Word bit asserts to
logical 1. If CLEN does not assert before CLSD expires, the CLOSE Relay Word bit does not
assert and the logic is reset. This logic permits the CLEN SEL
OGIC
control equation to supervise
relay initiated closes. See the Settings Example below.
Summary of Contents for SEL-300G
Page 1: ...SEL 300G Multifunction Generator Relay Instruction Manual 20060731 PM300G 01 NB ...
Page 4: ......
Page 6: ......
Page 138: ......
Page 166: ......
Page 170: ......
Page 288: ......
Page 290: ......
Page 328: ......
Page 442: ......
Page 456: ......
Page 458: ......
Page 468: ......
Page 470: ......
Page 512: ......
Page 516: ......
Page 518: ......
Page 552: ......
Page 554: ......
Page 560: ......
Page 578: ......
Page 626: ......
Page 724: ......
Page 728: ......