Relay Element Settings
2-7
SEL-300G Instruction Manual
Date Code 20060731
Calculate INOM using the following equation:
A
CTR
kV
•
73
.
1
1000
•
MVA
INOM
⎥⎦
⎤
⎢⎣
⎡
=
where
MVA
= generator rated output, MVA
kV
= generator rated phase-to-phase voltage, kV
CT
= phase current transformer ratio to one
The relay directional power, negative-sequence overcurrent, and differential elements
use the INOM setting.
DWG: M300G041
Generator
Grounding
Transformer
a:1
IN
VN
CTRN = CT Ratio to 1
PTRN = a
SEL-300G Relay
(partial)
Generator
Grounding
Transformer
a:1
IN
VN
CTRN = CT Ratio to 1
PTRN = 2 • a
SEL-300G Relay
(partial)
2:1
Optional
Auxiliary
Transformer
Figure 2.3: PTRN, CTRN Setting Examples