B-10
Firmware Upgrade Instructions
Date Code 20060731
SEL-300G Instruction Manual
Match Computer Communications Speed to the Relay
Step 6.
From the
Call
menu, choose
Disconnect
to terminate communication.
Step 7.
Correct the communications parameters:
a. From
the
File
menu, choose
Properties
.
b. Choose
Configure
.
c.
Change the computer communications speed to match the new data transmission
rate in the relay (Figure B.10).
d. Click
OK
twice.
Step 8.
Press
<Enter>
to check for the SEL
BOOT
!> prompt indicating that serial
communication is successful.
Figure B.10: Matching Computer to Relay Parameters
E. Download Existing Firmware
Copy the firmware presently in the relay, in case the new firmware upload is unsuccessful. To
make a backup of the existing firmware, the computer will need as much as 3 MB of free disk
space. This backup procedure takes 5–10 minutes at 38400 bps.
Step 1.
Type
SEN <Enter>
at the SEL
BOOT
!> prompt to initiate the firmware transfer from
the relay to the computer.
Step 2.
From the
Transfer
menu in
HyperTerminal
, select
Receive File
.
You should see a dialog box similar to Figure B.11.
Step 3.
Enter the pathname of a folder on the computer hard drive where you want to record
the existing relay firmware.
Summary of Contents for SEL-300G
Page 1: ...SEL 300G Multifunction Generator Relay Instruction Manual 20060731 PM300G 01 NB ...
Page 4: ......
Page 6: ......
Page 138: ......
Page 166: ......
Page 170: ......
Page 288: ......
Page 290: ......
Page 328: ......
Page 442: ......
Page 456: ......
Page 458: ......
Page 468: ......
Page 470: ......
Page 512: ......
Page 516: ......
Page 518: ......
Page 552: ......
Page 554: ......
Page 560: ......
Page 578: ......
Page 626: ......
Page 724: ......
Page 728: ......