SEL-3022 Transceiver
Instruction Manual
Date Code 20050615
Testing and Troubleshooting
Self-Tests
5.6
Cryptographic Manual—Do Not Copy
Self-Tests
The SEL-3022 has extensive self-test capabilities. You can determine the diagnostic
status of your SEL-3022 via the SEL-5809 Settings Software or the Status LED located
on the SEL-3022.
Under normal operating conditions the contact alarm is closed. If the SEL-3022 is
disabled the contact will open.
Table 5.3
SEL-3022 Self-Test Capabilities
Test
SEL-5809
Status:
Device
SEL-3022
Disable
Status
LED
Contact
Output
Alarm
Description
RAM
Pass
Yes
Toggle .5
second
Open
Performs a read and
write verification
Flash
Pass
Yes
Toggle .5
second (if
possible)
Open
Performs a checksum
calculation
Crypto-
graphic
Algorithm
Tests
NA
Yes
Toggle 1
second
Open
Checks known
answer tests for all
cryptographic func-
tions
802.11b
Self-Tests
NA
Yes
Toggle .5
second
Open
Indicates 802.11b
wireless device health
802.11b
SNR
dB
NA
NA
NA
Reports RF Signal-to-
Noise Ratio from
802.11b module
802.11b
Signal
dBm
NA
NA
NA
Reports RF Signal
Level from 802.11b
module
802.11b
Noise
dBm
NA
NA
NA
Reports RF Noise
Level from 802.11b
module
RNG Test
NA
Yes
Toggle 1
second
Open
Compares each block
with previous block
Zeroized
Key
NA
Yes
Toggle 2
seconds
Open
Indicates presence of
zeroized key material
Preliminary Copy
Summary of Contents for SEL-3022
Page 6: ...This page intentionally left blank Preliminary Copy ...
Page 12: ...This page intentionally left blank Preliminary Copy ...
Page 26: ...This page intentionally left blank Preliminary Copy ...
Page 42: ...This page intentionally left blank Preliminary Copy ...
Page 102: ...This page intentionally left blank Preliminary Copy ...
Page 104: ...This page intentionally left blank Preliminary Copy ...
Page 105: ...Preliminary Copy ...