7-26
Inputs, Outputs, Timers, and Other Control Logic
Date Code 20011205
SEL-311A Instruction Manual
The SEL-311A Relay can be programmed to operate similarly. Use three optoisolated inputs to
switch between the six setting groups in the SEL-311A Relay. In this example, optoisolated
inputs IN101, IN102, and IN103 on the relay are connected to a rotating selector switch in Figure
7.21.
Figure 7.21: Rotating Selector Switch Connected to Inputs IN101, IN102, and IN103 for
Active Setting Group Switching
The selector switch has multiple internal contacts arranged to assert inputs IN101, IN102, and
IN103, dependent on the switch position. As shown in Table 7.7, when the selector switch is
moved from one position to another, a different setting group is activated. The logic in Table 7.6
is implemented in the SEL
OGIC
control equation settings in Table 7.7.
Table 7.7: SEL
OGIC
Control Equation Settings for Rotating Selector Switch
Active Setting Group Switching
SS1 = !IN103 * !IN102 * IN101
= NOT(IN103) * NOT(IN102) * IN101
SS2 = !IN103 * IN102 * !IN101
= NOT(IN103) * IN102 * NOT(IN101)
SS3 = !IN103 * IN102 * IN101
= NOT(IN103) * IN102 * IN101
SS4 = IN103 * !IN102 * !IN101
= IN103 * NOT(IN102) * NOT(IN101)
SS5 = IN103 * !IN102 * IN101
= IN103 * NOT(IN102) * IN101
SS6 = IN103 * IN102 * !IN101
= IN103 * IN102 * NOT(IN101)
The settings in Table 7.7 are made in each setting Group 1 through 6.
Summary of Contents for SEL-311A
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 40: ......
Page 66: ......
Page 96: ......
Page 98: ......
Page 112: ......
Page 114: ......
Page 122: ......
Page 170: ......
Page 202: ......
Page 204: ......
Page 246: ......
Page 248: ......
Page 286: ......
Page 290: ......
Page 304: ......
Page 306: ......
Page 334: ......
Page 384: ......
Page 386: ......
Page 394: ......
Page 398: ......
Page 402: ......
Page 404: ......
Page 410: ......
Page 412: ......
Page 426: ......
Page 444: ......
Page 460: ......
Page 474: ......