S
ETTINGS
S
HEET
Page 6
OF
19
FOR THE
SEL-311A R
ELAY
Date
R
ELAY
S
ETTINGS
(S
ERIAL
P
ORT
C
OMMAND
SET
AND
F
RONT
P
ANEL
)
Date Code 20011205
Other Settings
Minimum trip duration time (4.00–16000.00 cycles in 0.25-cycle steps)
(see Figure 5.1)
TDURD =
Close failure time delay (OFF, 0.00-16000.00 cycles in 0.25-cycle steps)
(see Figure 6.1)
CFD =
Three-pole open time delay (0.00–60.00 cycles in 0.25-cycle steps)
(usually set for no more than a cycle; see Figure 5.3)
3POD =
Open pole option (52, 27)
OPO =
Three-pole open undervoltage (0.00–150.00 V secondary)
27PO =
Load detection phase pickup (OFF, 0.25–100.00A{5 A nom.};
0.05–20.00 A {1 A nom.}) (see Figure 5.3)
50LP =
SEL
OGIC
Control Equation Variable Timers (See Figures 7.23 and 7.24)
(Number of timer pickup/dropout settings dependent on preceding enable setting ESV = 1–16.)
SV1 Pickup Time (0.00–999999.00 cycles in 0.25-cycle steps)
SV1PU =
SV1 Dropout Time (0.00–999999.00 cycles in 0.25-cycle steps)
SV1DO =
SV2 Pickup Time (0.00–999999.00 cycles in 0.25-cycle steps)
SV2PU =
SV2 Dropout Time (0.00–999999.00 cycles in 0.25-cycle steps)
SV2DO =
SV3 Pickup Time (0.00–999999.00 cycles in 0.25-cycle steps)
SV3PU =
SV3 Dropout Time (0.00–999999.00 cycles in 0.25-cycle steps)
SV3DO =
SV4 Pickup Time (0.00–999999.00 cycles in 0.25-cycle steps)
SV4PU =
SV4 Dropout Time (0.00–999999.00 cycles in 0.25-cycle steps)
SV4DO =
SV5 Pickup Time (0.00–999999.00 cycles in 0.25-cycle steps)
SV5PU =
SV5 Dropout Time (0.00–999999.00 cycles in 0.25-cycle steps)
SV5DO =
SV6 Pickup Time (0.00–999999.00 cycles in 0.25-cycle steps)
SV6PU =
SV6 Dropout Time (0.00–999999.00 cycles in 0.25-cycle steps)
SV6DO =
SV7 Pickup Time (0.00–16000.00 cycles in 0.25-cycle steps)
SV7PU =
SV7 Dropout Time (0.00–16000.00 cycles in 0.25-cycle steps)
SV7DO =
SV8 Pickup Time (0.00–16000.00 cycles in 0.25-cycle steps)
SV8PU =
SV8 Dropout Time (0.00–16000.00 cycles in 0.25-cycle steps)
SV8DO =
SV9 Pickup Time (0.00–16000.00 cycles in 0.25-cycle steps)
SV9PU =
SV9 Dropout Time (0.00–16000.00 cycles in 0.25-cycle steps)
SV9DO =
SV10 Pickup Time (0.00–16000.00 cycles in 0.25-cycle steps)
SV10PU =
SV10 Dropout Time (0.00–16000.00 cycles in 0.25-cycle steps)
SV10DO =
SV11 Pickup Time (0.00–16000.00 cycles in 0.25-cycle steps)
SV11PU =
SV11 Dropout Time (0.00–16000.00 cycles in 0.25-cycle steps)
SV11DO =
SV12 Pickup Time (0.00–16000.00 cycles in 0.25-cycle steps)
SV12PU =
SV12 Dropout Time (0.00–16000.00 cycles in 0.25-cycle steps)
SV12DO =
SV13 Pickup Time (0.00–16000.00 cycles in 0.25-cycle steps)
SV13PU =
SV13 Dropout Time (0.00–16000.00 cycles in 0.25-cycle steps)
SV13DO =
Summary of Contents for SEL-311A
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 40: ......
Page 66: ......
Page 96: ......
Page 98: ......
Page 112: ......
Page 114: ......
Page 122: ......
Page 170: ......
Page 202: ......
Page 204: ......
Page 246: ......
Page 248: ......
Page 286: ......
Page 290: ......
Page 304: ......
Page 306: ......
Page 334: ......
Page 384: ......
Page 386: ......
Page 394: ......
Page 398: ......
Page 402: ......
Page 404: ......
Page 410: ......
Page 412: ......
Page 426: ......
Page 444: ......
Page 460: ......
Page 474: ......