Date Code 20011205
Installation
2-13
SEL-311A Instruction Manual
If an output contact is operating as an “extra alarm” (driven by the same signal that operates the
dedicated ALARM output contact), it will be in the opposite state of the dedicated ALARM
output contact in a standard relay shipment. In a standard relay shipment, the dedicated ALARM
output contact comes as a “b” type output contact and all the other output contacts (including the
“extra alarm”) come as “a” type output contacts.
The output contact type for any output contact can be changed (see preceding subsection
Output
Contact Jumpers
). Thus, the dedicated ALARM output contact and the “extra alarm” output
contact can be configured as the same output contact type if desired (e.g., both can be configured
as “b” type output contacts).
Password and Breaker Jumpers
Table 2.3: Password and Breaker Jumper Operation
Jumper
Jumper Position
Function
Password
JMP6-A
ON
(in place)
Disable password protection
1
for serial ports and
front panel.
OFF
(removed/not in place)
Enable password protection
1
for serial ports and
front panel. Passwords are enabled in a standard
relay shipment.
Breaker
JMP6-B
ON
(in place)
Enable serial port commands OPEN, CLOSE, and
PULSE
2
. These commands are disabled in a
standard relay shipment.
OFF
(removed/not in place)
Disable serial port commands OPEN, CLOSE, and
PULSE
2
. These commands are disabled in a
standard relay shipment.
1
View or set the passwords with the PASSWORD command (see
Section 10: Serial Port
Communications and Commands
).
2
The OPEN, CLOSE, and PULSE commands are used primarily to assert output contacts for
circuit breaker control or testing purposes (see
Section 10: Serial Port Communications and
Commands
).
Note that JMP6 in Figure 2.7 has multiple jumpers A through D. Jumpers A and B are used (see
Table 2.3). Since jumpers C and D are not used, the positions (ON or OFF) of jumpers C and D
are of no consequence.
EIA-232 Serial Port Voltage Jumpers
The jumpers listed in Table 2.4 connect or disc5 Vdc to Pin 1 on the corresponding
EIA
-
232 serial ports. The +5 Vdc is rated at 0.5 A maximum for each port. See Table 10.1 in
Section 10: Serial Port Communications and Commands
for EIA
-
232 serial port pin functions.
In a standard relay shipment, the jumpers are “OFF” (removed/not in place) so that the +5 Vdc is
not connected to Pin 1 on the corresponding EIA-232 serial ports. Put the jumpers “ON” (in
place) so that the +5 Vdc is connected to Pin 1 on the corresponding EIA-232 serial ports.
Summary of Contents for SEL-311A
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 40: ......
Page 66: ......
Page 96: ......
Page 98: ......
Page 112: ......
Page 114: ......
Page 122: ......
Page 170: ......
Page 202: ......
Page 204: ......
Page 246: ......
Page 248: ......
Page 286: ......
Page 290: ......
Page 304: ......
Page 306: ......
Page 334: ......
Page 384: ......
Page 386: ......
Page 394: ......
Page 398: ......
Page 402: ......
Page 404: ......
Page 410: ......
Page 412: ......
Page 426: ......
Page 444: ......
Page 460: ......
Page 474: ......