Date Code 20011205
Setting SEL
OGIC
Control Equations
F-9
SEL-311A Instruction Manual
The SEL
OGIC
control equation settings as a whole are limited to no more than 447 elements and
49 rising-edge or falling-edge operators.
SEL
OGIC
control equation settings that are set directly to 1 (logical 1) or 0 (logical 0) also have
to be included in these limitations—each such setting counted as one element.
After SEL
OGIC
control equation settings changes have been made and the settings are saved, the
SEL-311A responds with the following message:
xxx Elements and yy Edges remain available
indicating that “xxx” Relay Word bits can still be used and “yy” rising or falling edge operators
can still be applied in the SEL
OGIC
control equations for the particular settings group.
P
ROCESSING
O
RDER AND
P
ROCESSING
I
NTERVAL
The relay elements and logic (and corresponding SEL
OGIC
control equation settings and resultant
Relay Word bits) are processed in a predetermined order. They are processed every quarter-
cycle (1/4-cycle), and the Relay Word bit states (logical 1 or logical 0) are updated with each
quarter-cycle pass. Thus, the relay-processing interval is 1/4-cycle. Once a Relay Word bit is
asserted, it retains the state (logical 1 or logical 0) until it is updated again in the next processing
interval. Logical outputs of SEL
OGIC
control equations may be delayed by 1/4-cycle due to relay
element processing order.
Summary of Contents for SEL-311A
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 40: ......
Page 66: ......
Page 96: ......
Page 98: ......
Page 112: ......
Page 114: ......
Page 122: ......
Page 170: ......
Page 202: ......
Page 204: ......
Page 246: ......
Page 248: ......
Page 286: ......
Page 290: ......
Page 304: ......
Page 306: ......
Page 334: ......
Page 384: ......
Page 386: ......
Page 394: ......
Page 398: ......
Page 402: ......
Page 404: ......
Page 410: ......
Page 412: ......
Page 426: ......
Page 444: ......
Page 460: ......
Page 474: ......