Date Code 20011205
Distance and Overcurrent Elements
3-19
SEL-311A Instruction Manual
T
IME
-O
VERCURRENT
E
LEMENTS
Phase Time-Overcurrent Elements
One phase time-overcurrent element is available. The element is enabled with the E51P enable
setting as follows:
Table 3.2: Available Phase Time-Overcurrent Elements
Time-Overcurrent
Element
Enabled with
Setting
Operating Current
See Figure
51PT
E51P = Y
I
ABC
, maximum of A-, B-, and
C-phase currents
51PT Element Settings Ranges
The 51PT phase time-overcurrent element has the following settings:
Table 3.3: Phase Time-Overcurrent Element (Maximum Phase) Settings
Setting Definition
Range
51PP
pickup
0.50–16.00 A secondary (5 A nominal phase current
inputs, IA, IB, IC)
0.10–3.20 A secondary (1 A nominal phase current
inputs, IA, IB, IC)
51PC
curve type
U1–U5 (US curves) see Figure 9.1–Figure 9.10
C1–C5 (IEC curves)
51PTD
time dial
0.50–15.00 (US curves) see Figure 9.1–Figure 9.10
0.05–1.00 (IEC curves)
51PRS electromechanical
reset timing
Y = Enable electromechanical reset timing
N = 1 cycle reset delay
51PTC SEL
OGIC
control
equation torque
control setting
Relay Word bits referenced in Tables 9.3 and 9.4
or
set directly to logical 1—see note below
Note
: SEL
OGIC
control equation torque control settings (e.g., 51PTC) cannot be set directly to
logical 0.
See
Section 9: Setting the Relay
for additional time-overcurrent element setting information.
Summary of Contents for SEL-311A
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 40: ......
Page 66: ......
Page 96: ......
Page 98: ......
Page 112: ......
Page 114: ......
Page 122: ......
Page 170: ......
Page 202: ......
Page 204: ......
Page 246: ......
Page 248: ......
Page 286: ......
Page 290: ......
Page 304: ......
Page 306: ......
Page 334: ......
Page 384: ......
Page 386: ......
Page 394: ......
Page 398: ......
Page 402: ......
Page 404: ......
Page 410: ......
Page 412: ......
Page 426: ......
Page 444: ......
Page 460: ......
Page 474: ......