Date Code 20011205
Trip and Target Logic
5-3
SEL-311B Instruction Manual
Figure 5.2: Minimum Trip Duration Timer Operation (See Bottom of Figure 5.1)
The OPEN command is included in the trip logic in the factory settings:
TR = … + OC
Relay Word bit OC asserts for execution of the OPEN Command. See
OPE Command (Open
Breaker)
in
Section 10: Serial Port Communications and Commands
for more information on
the OPEN Command. More discussion follows later on the factory settings for setting TR.
If a user wants to supervise the OPEN command with optoisolated input IN105, the following
setting is made:
TR = … + OC * IN105
With this setting, the OPEN command can provide a trip only if optoisolated input IN105 is
asserted. This is just one OPEN command supervision example—many variations are possible.
To prevent the execution of the OPEN command from initiating reclosing, Relay Word bit OC is
entered in the SEL
OGIC
control equation setting 79DTL (Drive-to-Lockout) in the factory
settings. See the Note in the Lockout State discussion, following Table 6.1.
Unlatch Trip
Once Relay Word bit TRIP is asserted to logical 1, it remains asserted at logical 1 until all the
following conditions come true:
·
Minimum Trip Duration Timer stops timing (logic output of the TDURD timer goes to
logical 0)
·
Output of OR-1 gate in Figure 5.1 deasserts to logical 0
Summary of Contents for SEL-311B
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 26: ......
Page 122: ......
Page 124: ......
Page 138: ......
Page 168: ......
Page 172: ......
Page 254: ......
Page 282: ......
Page 306: ......
Page 348: ......
Page 364: ......
Page 366: ......
Page 448: ......
Page 460: ......
Page 466: ......
Page 476: ......
Page 482: ......
Page 494: ......
Page 500: ......
Page 522: ......
Page 526: ......
Page 528: ......
Page 534: ......
Page 536: ......
Page 550: ......
Page 570: ......
Page 586: ......
Page 600: ......