Date Code 20011205
Close and Reclose Logic
6-9
SEL-311B Instruction Manual
If 79CLS remains deasserted to logical 0 during this entire 79CLSD time window, when the time
window times out, the following occurs:
·
No automatic reclosing takes place.
·
Relay Word bit RCSF (Reclose Supervision Failure indication) asserts to logical 1 for
one processing interval.
·
The reclosing relay is driven to the Lockout State.
The logic in the bottom of Figure 6.2 is explained in more detail in the following text.
Set Reclose Supervision Logic (Bottom of Figure 6.2)
Refer to the bottom of Figure 6.2. If all the following are true:
·
The close logic output CLOSE is not asserted (Relay Word bit CLOSE = logical 0).
·
The reclosing relay is not in the Lockout State (Relay Word bit 79LO = logical 0).
·
The circuit breaker is open (52A = logical 0).
·
The reclose initiation condition (79RI) is not making a rising edge (logical 0 to
logical 1) transition.
·
The Reclose Supervision Limit Timer is not timed out (Relay Word bit RCSF =
logical 0).
then a reclosing relay open interval time-out seals in Figure 6.2. Then, when 79CLS asserts to
logical 1, the sealed-in reclosing relay open interval time-out condition will propagate through
Figure 6.2 and on to the close logic in Figure 6.1.
Unlatch Reclose Supervision Logic (Bottom of Figure 6.2)
Refer to the bottom of Figure 6.2. If the reclosing relay open interval time-out condition is
sealed-in, it stays sealed-in until one of the following occurs:
·
The close logic output CLOSE (also see Figure 6.1) asserts (Relay Word bit CLOSE =
logical 1).
·
The reclosing relay goes to the Lockout State (Relay Word bit 79LO = logical 1).
·
The circuit breaker closes (52A = logical 1).
·
The reclose initiation condition (79RI) makes a rising edge (logical 0 to logical 1)
transition.
·
SEL
OGIC
control equation setting 79CLS asserts (79CLS = logical 1).
·
The Reclose Supervision Limit Timer times out (Relay Word bit RCSF = logical 1 for
one processing interval).
The Reclose Supervision Limit Timer is inoperative if setting 79CLSD = OFF. With
79CLSD = OFF, reclose supervision condition 79CLS is not time limited. When an open
interval times out, reclose supervision condition 79CLS is checked indefinitely until one of the
other above unlatch conditions comes true.
Summary of Contents for SEL-311B
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 26: ......
Page 122: ......
Page 124: ......
Page 138: ......
Page 168: ......
Page 172: ......
Page 254: ......
Page 282: ......
Page 306: ......
Page 348: ......
Page 364: ......
Page 366: ......
Page 448: ......
Page 460: ......
Page 466: ......
Page 476: ......
Page 482: ......
Page 494: ......
Page 500: ......
Page 522: ......
Page 526: ......
Page 528: ......
Page 534: ......
Page 536: ......
Page 550: ......
Page 570: ......
Page 586: ......
Page 600: ......