Date Code 20011205
Close and Reclose Logic
6-17
SEL-311B Instruction Manual
timing. If the subsequent second reclosure is not successful, the relay goes to the Lockout State.
See the example time line in Figure 6.6.
Figure 6.6: Reclosing Sequence From Reset to Lockout with Example Settings
SEL
OGIC
control equation setting 79STL (stall open interval timing) can be set to control open
interval timing (see
Skip Shot and Stall Open Interval Timing Settings [79SKP and 79STL,
Respectively]
later in this subsection).
Determination of Number of Reclosures (Last Shot)
The number of reclosures is equal to the number of open interval time settings that precede the
first open interval time setting set equal to zero. The “last shot” value is also equal to the number
of reclosures.
In the above example settings, two set open interval times precede open interval 3 time, which is
set to zero (79OI3 = 0.00):
79OI1 =
30.00
79OI2 =
600.00
79OI3 =
0.00
For this example:
The number of reclosures (last shot) is 2, the number of set open interval times that precede the
first open interval set to zero.
Observe Shot Counter Operation
Observe the reclosing relay shot counter operation, especially during testing, with the front-panel
shot counter screen (accessed via the OTHER pushbutton). See
Functions Unique to the
Front-Panel Interface
in
Section 11: Front-Panel Interface
.
Summary of Contents for SEL-311B
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 26: ......
Page 122: ......
Page 124: ......
Page 138: ......
Page 168: ......
Page 172: ......
Page 254: ......
Page 282: ......
Page 306: ......
Page 348: ......
Page 364: ......
Page 366: ......
Page 448: ......
Page 460: ......
Page 466: ......
Page 476: ......
Page 482: ......
Page 494: ......
Page 500: ......
Page 522: ......
Page 526: ......
Page 528: ......
Page 534: ......
Page 536: ......
Page 550: ......
Page 570: ......
Page 586: ......
Page 600: ......