Date Code 20011205
Close and Reclose Logic
6-27
SEL-311B Instruction Manual
When the relay is in the Reclose Cycle State, Relay Word bit 79CY is asserted to logical 1.
Thus, the 79BRS setting can function to block reset timing if time-overcurrent pickup 51P or
51G is picked up while the relay is in the Reclose Cycle State. This helps prevent repetitive
"trip-reclose" cycling.
Additional Settings Example 2
If the block reset timing setting is:
79BRS = 51P + 51G
then reset timing is blocked if time-overcurrent pickup 51P or 51G is picked up, regardless of the
reclosing relay state.
Sequence Coordination Setting (79SEQ)
The 79SEQ setting is applicable to distribution applications, for transmission system applications
set 79SEQ = 0. See the SEL-351 Instruction Manual for a description of setting 79SEQ.