7-6
Inputs, Outputs, Timers, and Other Control Logic
Date Code 20011205
SEL-311B Instruction Manual
Table 7.1: Correspondence Between Local Control Switch Positions and Label Settings
Switch Position
Label
Setting
Setting Definition
Logic State
not applicable
NLB
n
Name of Local Control
Switch
not applicable
ON SLB
n
“Set” Local bit LBn
logical 1
OFF CLB
n
“Clear” Local bit LBn
logical 0
MOMENTARY PLB
n
“Pulse” Local bit LBn
logical 1 for one processing
interval
Note the first setting in Table 7.1 (NLB
n
) is the overall switch name setting. Make each label
setting through the serial port using the command
SET T
. View these settings using the serial
port command
SHO T
(see
Section 9: Setting the Relay
and
Section 10: Serial Port
Communications and Commands
).
Local Control Switch Types
Configure any local control switch as one of the following three switch types:
ON/OFF Switch
Local bit LB
n
is in either the ON (LB
n
= logical 1) or OFF (LB
n
= logical 0) position.
Figure 7.4: Local Control Switch Configured as an ON/OFF Switch
OFF/MOMENTARY Switch
The local bit LB
n
is maintained in the OFF (LB
n
= logical 0) position and pulses to the
MOMENTARY (LB
n
= logical 1) position for one processing interval (1/4 cycle).
Summary of Contents for SEL-311B
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 26: ......
Page 122: ......
Page 124: ......
Page 138: ......
Page 168: ......
Page 172: ......
Page 254: ......
Page 282: ......
Page 306: ......
Page 348: ......
Page 364: ......
Page 366: ......
Page 448: ......
Page 460: ......
Page 466: ......
Page 476: ......
Page 482: ......
Page 494: ......
Page 500: ......
Page 522: ......
Page 526: ......
Page 528: ......
Page 534: ......
Page 536: ......
Page 550: ......
Page 570: ......
Page 586: ......
Page 600: ......