7-16
Inputs, Outputs, Timers, and Other Control Logic
Date Code 20011205
SEL-311B Instruction Manual
Figure 7.14: Latch Control Switch Operation Time Line
Use a Remote Bit Instead to Enable/Disable the Reclosing Relay
Use a remote bit to enable/disable the reclosing relay, instead of an optoisolated input. For
example, substitute remote bit RB1 for optoisolated input IN104 in the settings accompanying
Figure 7.13:
SET1 = /RB1 * !LT1
[= (rising edge of remote bit RB1) AND NOT(LT1)]
RST1 = /RB1 * LT1
[= (rising edge of remote bit RB1) AND LT1]
79DTL = !LT1
[= NOT(LT1); drive-to-lockout setting]
Pulse remote bit RB1 to enable reclosing, pulse remote bit RB1 to disable reclosing, etc.—much
like the operation of optoisolated input IN104 in the previous example. Remote bits (Relay
Word bits RB1 through RB16) are operated through the serial port. See Figure 7.9 and
Section 10: Serial Port Communications and Commands
for more information on remote bits.
These are just a few control logic examples—many variations are possible.
Summary of Contents for SEL-311B
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 26: ......
Page 122: ......
Page 124: ......
Page 138: ......
Page 168: ......
Page 172: ......
Page 254: ......
Page 282: ......
Page 306: ......
Page 348: ......
Page 364: ......
Page 366: ......
Page 448: ......
Page 460: ......
Page 466: ......
Page 476: ......
Page 482: ......
Page 494: ......
Page 500: ......
Page 522: ......
Page 526: ......
Page 528: ......
Page 534: ......
Page 536: ......
Page 550: ......
Page 570: ......
Page 586: ......
Page 600: ......