Date Code 20011205
Introduction and Specifications
1-11
SEL-311B Instruction Manual
Relay Element Settings Ranges and Accuracies
Metering Accuracy
Voltages V
A
, V
B
, V
C
, V
S
:
±0.67 V secondary
Currents I
A
, I
B
, I
C
, I
P
:
±0.05 A secondary (5 A nominal)
±0.01 A secondary (1 A nominal)
Substation Battery Voltage Monitor Specifications
Pickup Range:
20–300 Vdc, 1 Vdc steps
Pickup Accuracy:
±2% of setting
Timer Specifications
Reclosing Relay Pickup:
0.00–999,999.00 cycles, 0.25-cycle steps
Other Timers:
0.00–16,000.00 cycles, 0.25-cycle steps
Pickup/dropout accuracy for
all timers:
±0.25 cycle and ±0.1% of setting
Mho Phase Distance Elements
Zones 1–3 Impedance Reach
Setting Range:
OFF, 0.05 to 64
Ω
sec, 0.01
Ω
steps (5 A nominal)
OFF, 0.25 to 320
Ω
sec, 0.01
Ω
steps (1 A nominal)
Minimum sensitivity is controlled by the pickup of the supervising
phase-to-phase overcurrent elements for each zone.
Accuracy:
±
5% of setting at line angle for 30
≤
SIR
≤
60
±
3% of setting at line angle for SIR < 30
Transient Overreach:
< 5% of setting plus steady state accuracy
Zones 1–3 Phase-to-Phase Current Fault Detectors (FD)
Setting Range:
0.5–170.00 A
P-P
secondary, 0.01 A steps (5 A nominal)
0.1–34.00 A
P-P
secondary, 0.01 A steps (1 A nominal)
Accuracy:
±
0.05 A and ±3% of setting (5 A nominal)
±
0.01 A and ±3% of setting (1 A nominal)
Transient Overreach:
< 5% of pickup
Max. Operating Time:
See pickup and reset time curves in Figure 3.14 and Figure 3.15
Summary of Contents for SEL-311B
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 26: ......
Page 122: ......
Page 124: ......
Page 138: ......
Page 168: ......
Page 172: ......
Page 254: ......
Page 282: ......
Page 306: ......
Page 348: ......
Page 364: ......
Page 366: ......
Page 448: ......
Page 460: ......
Page 466: ......
Page 476: ......
Page 482: ......
Page 494: ......
Page 500: ......
Page 522: ......
Page 526: ......
Page 528: ......
Page 534: ......
Page 536: ......
Page 550: ......
Page 570: ......
Page 586: ......
Page 600: ......