13-44
Testing and Troubleshooting
Date Code 20011205
SEL-311B Instruction Manual
Table 13.5: Relay Self-Tests
Self-Test
Condition
Limits
Protection
Disabled
ALARM
Output
Description
IA, IB, IC,
IP, VA, VB,
VC, VS
Offset
Warning
30 mV
No
Pulsed
Measures the dc offset at
each of the input
channels every 10
seconds.
Master
Offset
Warning
20 mV
No
Pulsed
Measures the dc offset at
the A/D every 10
seconds.
Failure
30
mV
Yes
Latched
+5 V PS
Warning
+4.80 V
+5.20 V
No
Pulsed
Measures the +5 V power
supply every 10 seconds.
Failure
+4.65
V
+5.40 V
Yes Latched
+5 V REG
Warning
+4.75 V
+5.20 V,
-4.75 V
-5.25 V
No
Pulsed
Measures the regulated
5 V power supply every
10 seconds.
Failure
+4.50
V
+5.40 V,
-4.50 V
-5.50 V
Yes Latched
+12 V PS
Warning
+11.50 V
+12.50 V
No
Pulsed
Measures the 12 V power
supply every 10 seconds.
Failure
+11.20 V
+14.00 V
Yes Latched
+15 V PS
Warning
+14.40 V
+15.60 V
No
Pulsed
Measures the 15 V power
supply every 10 seconds.
Failure
+14.00 V
+16.00 V
Yes Latched
TEMP Warning
-40
°
C
+85
°
C
No
Measures the temperature
at the A/D voltage
reference every 10
seconds.
Failure
-50
°
C
+100
°
C
Yes Latched
Summary of Contents for SEL-311B
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 26: ......
Page 122: ......
Page 124: ......
Page 138: ......
Page 168: ......
Page 172: ......
Page 254: ......
Page 282: ......
Page 306: ......
Page 348: ......
Page 364: ......
Page 366: ......
Page 448: ......
Page 460: ......
Page 466: ......
Page 476: ......
Page 482: ......
Page 494: ......
Page 500: ......
Page 522: ......
Page 526: ......
Page 528: ......
Page 534: ......
Page 536: ......
Page 550: ......
Page 570: ......
Page 586: ......
Page 600: ......