Date Code 20011205
Application Settings for SEL-221 Series Relays
14-23
SEL-311B Instruction Manual
SEL-221F-3
Relay Word Bit
Equivalent SEL-311B
SEL
OGIC
Expression
Z3T Z3T
3P21
M3P * !32QF
32Q
32GF + 32QF
67N 67G1
51NP 51G
51NT 51GT
50NG None
50P None
50H 50P1
IN1 IN101
REJO None
LOP ILOP
BFT SV1T
27S !59VS
27P !59VP
59S 59VS
59P 59VP
SSC 25A1
VSC
(LSDP)
(LPDS)
SV2T
(59VS * !59VP * !50L)
(59VP * !59VS * !50L)
For example, the factory default setting for MRC in the SEL-221F-3 is shown in Table 14.9.
From Table 14.7, the equivalent SEL-311B SEL
OGIC
control equation to MRC is 79DTL.
Constructing the logical OR of the equivalent of each element selected in the MRC mask from
Table 14.8 gives:
79DTL = Z3T + 51GT
Include the open command OC:
79DTL = Z3T + 51GT + OC
This is the default SEL
OGIC
control equation for 79DTL when APP = 221F3.
When setting APP = 221F3, the SEL-311B automatically sets the following SEL
OGIC
control
equations. Change the settings just as you would change the Mask Logic settings in an
SEL-221F-3 to customize the relay logic.
Summary of Contents for SEL-311B
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 26: ......
Page 122: ......
Page 124: ......
Page 138: ......
Page 168: ......
Page 172: ......
Page 254: ......
Page 282: ......
Page 306: ......
Page 348: ......
Page 364: ......
Page 366: ......
Page 448: ......
Page 460: ......
Page 466: ......
Page 476: ......
Page 482: ......
Page 494: ......
Page 500: ......
Page 522: ......
Page 526: ......
Page 528: ......
Page 534: ......
Page 536: ......
Page 550: ......
Page 570: ......
Page 586: ......
Page 600: ......