Date Code 20011205
Loss-of-Potential, CCVT Transient Detection,
4-9
Load-Encroachment, and Directional Element Logic
SEL-311B Instruction Manual
D
IRECTIONAL
C
ONTROL FOR
G
ROUND
D
ISTANCE AND
R
ESIDUAL
G
ROUND
O
VERCURRENT
E
LEMENTS
Setting E32 configures directional control for distance and overcurrent elements. Setting E32 and
other directional control settings are described in the following subsection
Directional Control
Settings
.
Three directional elements are available to control the ground distance and residual ground
overcurrent elements. These three directional elements are:
·
Negative-sequence voltage-polarized directional element
·
Zero-sequence voltage-polarized directional element
·
Channel IP current-polarized directional element
Figure 4.5: General Logic Flow of Directional Control for Ground Distance and Residual
Ground Overcurrent Elements
Figure 4.5 gives an overview of how these directional elements are enabled and routed to control
the ground distance and residual ground overcurrent elements.
Summary of Contents for SEL-311B
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 26: ......
Page 122: ......
Page 124: ......
Page 138: ......
Page 168: ......
Page 172: ......
Page 254: ......
Page 282: ......
Page 306: ......
Page 348: ......
Page 364: ......
Page 366: ......
Page 448: ......
Page 460: ......
Page 466: ......
Page 476: ......
Page 482: ......
Page 494: ......
Page 500: ......
Page 522: ......
Page 526: ......
Page 528: ......
Page 534: ......
Page 536: ......
Page 550: ......
Page 570: ......
Page 586: ......
Page 600: ......