7-10
Inputs, Outputs, Timers, and Other Control Logic
Date Code 20011205
SEL-311B Instruction Manual
If settings are changed for a setting group other than the active setting group, there is no
interruption of the local bits (the relay is not momentarily disabled).
If a local control switch is made inoperable because of a settings change (i.e., the corresponding
label settings are nulled), the corresponding local bit is then fixed at logical 0, regardless of the
local bit state before the settings change. If a local control switch is made newly operable
because of a settings change (i.e., the corresponding label settings are set), the corresponding
local bit starts out at logical 0.
R
EMOTE
C
ONTROL
S
WITCHES
Remote control switches are operated via the serial communications port only (see
CON
Command (Control Remote Bit)
in
Section 10: Serial Port Communications and Commands
).
Figure 7.9: Remote Control Switches Drive Remote Bits RB1 Through RB16
The outputs of the remote control switches in Figure 7.9 are Relay Word bits RB
n
(
n
= 1 to 16),
called remote bits. Use these remote bits in SEL
OGIC
control equations.
Any given remote control switch can be put in one of the following three positions:
ON (logical
1)
OFF (logical
0)
MOMENTARY (logical 1 for one processing interval)
Summary of Contents for SEL-311B
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 26: ......
Page 122: ......
Page 124: ......
Page 138: ......
Page 168: ......
Page 172: ......
Page 254: ......
Page 282: ......
Page 306: ......
Page 348: ......
Page 364: ......
Page 366: ......
Page 448: ......
Page 460: ......
Page 466: ......
Page 476: ......
Page 482: ......
Page 494: ......
Page 500: ......
Page 522: ......
Page 526: ......
Page 528: ......
Page 534: ......
Page 536: ......
Page 550: ......
Page 570: ......
Page 586: ......
Page 600: ......