Date Code 20011205
Application Settings for SEL-221 Series Relays
14-9
SEL-311B Instruction Manual
SEL
OGIC
Variables Equations
SV1 =
25A1
SV2
= 59VP * !59VS * !50L * LT1 + 59VS * !59VP * !50L * LT2
SV3
= M3P + Z3G
SV4 =
0
SEL
OGIC
Latch Equations
The SEL
OGIC
latch equations emulate the SEL-221F setting PSVC for settings P, S, and E.
Table 14.5: SEL-221F Setting PSVC for Settings P, S, and E
SEL-311B
Relay Word Bit
PSVC = S
(Default)
PSVC = P
PSVC = E
SET1
= 0
= 1
= 1
RST1
= 1
= 0
= 0
SET2
= 1
= 0
= 1
RST2
= 0
= 1
= 0
The following contact input assignments are made automatically by the SEL-311B when setting
APP = 221F. These assignments cannot be changed unless setting APP is changed back to
APP = 311B.
Default Contact Input Functions
IN101
= Programmable Input (Direct Trip)
IN102
= PT ( Permit trip)
IN103
= BT (Block trip)
IN104
= CL (Close breaker)
IN105 =
52A
IN106
= EXT (External event report trigger)
Summary of Contents for SEL-311B
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 26: ......
Page 122: ......
Page 124: ......
Page 138: ......
Page 168: ......
Page 172: ......
Page 254: ......
Page 282: ......
Page 306: ......
Page 348: ......
Page 364: ......
Page 366: ......
Page 448: ......
Page 460: ......
Page 466: ......
Page 476: ......
Page 482: ......
Page 494: ......
Page 500: ......
Page 522: ......
Page 526: ......
Page 528: ......
Page 534: ......
Page 536: ......
Page 550: ......
Page 570: ......
Page 586: ......
Page 600: ......