Date Code 20011205
Distance, Overcurrent, Voltage,
3-11
and Synchronism Check Elements
SEL-311B Instruction Manual
|IA|
50L1
(Setting)
32GF
_
+
_
+
|IG|
50GZ1
(Setting)
See Note 1 mAG < Z1MG • X1
M311B037a
FSA
CVTBL
3PO
ILOP
VPOLV
Zone 1 A-Phase Mho Ground Distance Logic.
B and C Phase Are Similar.
Note 1: mAG = A-Phase to Ground Distance Calculation
Z1MG = Zone 1 Distance Setting
X1 = Zone 1 Extension
MAG1
MBG1
MCG1
Z1G
Relay
Word
Bit
Relay
Word
Bits
(unless
noted)
Relay
Word
Bits
5
4
2
1
3
From Figure 4.12
From Figure 4.1
From Figure 4.2
From Figure 3.11
From Figure 5.3
Figure 3.7: Zone 1 Mho Ground Distance Logic