3-16
Distance, Overcurrent, Voltage,
Date Code 20011205
and Synchronism Check Elements
SEL-311B Instruction Manual
EZ1EXT = N
(Setting)
51Q
0
Z1EXTD
S
R
Q
Z1X
M311B040a
51G
M1P
Z1G
M2P
Z2G
3PO
Z1X
0
1
X1
(See and )
1.0
Z1EXTM
5
4
2
1
3
6
4
3
7
From Figure 3.20
From Figure 3.5
From Figure 3.19
From Figure 3.8
From Figure 3.4
From Figure 5.3
From Figure 3.7
Figure 3.11: Zone 1 Extension Logic
Zone Time Delay Elements
The SEL-311B Relay supports two philosophies of zone timing: independent or common timing
(see Figure 3.12). For the independent timing mode, the phase and ground distance elements
drive separate timers for each zone. For the common mode, the phase and ground distance
elements both drive a common timer.
Common Timer Settings:
Z1D through Z3D
Independent Phase Timer Settings:
Z1PD through Z3PD
Independent Ground Timer Settings:
Z1GD through Z3GD
Pickup Ranges:
OFF, 0.00–16,000.00 cycles, 0.25-cycle steps
Pickup and dropout accuracy for all timers: ±0.25 cycle and ±0.1% of setting
Select independent zone timing by using relay words M
n
PT and Z
n
GT (where
n
is the protection
zone number) in the appropriate SEL
OGIC
trip equation.
TR = M1P + Z1G +
M2PT
+
Z2GT
+ 51GT + 51QT
Select common zone timing by using relay words Z
n
T (where
n
is the protection zone number) in
the appropriate SEL
OGIC
trip equation.
TR = M1P + Z1G +
Z2T
+ 51GT + 51QT
Summary of Contents for SEL-311B
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 26: ......
Page 122: ......
Page 124: ......
Page 138: ......
Page 168: ......
Page 172: ......
Page 254: ......
Page 282: ......
Page 306: ......
Page 348: ......
Page 364: ......
Page 366: ......
Page 448: ......
Page 460: ......
Page 466: ......
Page 476: ......
Page 482: ......
Page 494: ......
Page 500: ......
Page 522: ......
Page 526: ......
Page 528: ......
Page 534: ......
Page 536: ......
Page 550: ......
Page 570: ......
Page 586: ......
Page 600: ......