Date Code 20011205
Distance, Overcurrent, Voltage,
3-29
and Synchronism Check Elements
SEL-311B Instruction Manual
Figure 3.19: Residual Ground Time-Overcurrent Element 51GT
Settings Ranges
Table 3.5: Residual Ground Time-Overcurrent Element Settings
Setting Definition
Range
51GP
pickup
OFF, 0.50–16.00 A secondary (5 A nominal phase
current inputs, IA, IB, IC)
OFF, 0.10–3.20 A secondary (1 A nominal phase
current inputs, IA, IB, IC)
51GC
curve type
U1–U5 (US curves) see Figure 9.1–Figure 9.10
C1–C5 (IEC curves)
51GTD
time dial
0.50–15.00 (US curves) see Figure 9.1–Figure 9.10
0.05–1.00 (IEC curves)
51GRS electromechanical
reset timing
Y = Enable electromechanical reset timing
N = 1 cycle reset delay
51GTC SEL
OGIC
control
equation torque
control setting
Relay Word bits referenced in Tables 9.3 and 9.4
or
set directly to logical 1—see note below.
Note
: SEL
OGIC
control equation torque control settings (e.g., 51GTC) cannot be set directly to
logical 0.
See
Section 9: Setting the Relay
for additional time-overcurrent element settings information.
Summary of Contents for SEL-311B
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 26: ......
Page 122: ......
Page 124: ......
Page 138: ......
Page 168: ......
Page 172: ......
Page 254: ......
Page 282: ......
Page 306: ......
Page 348: ......
Page 364: ......
Page 366: ......
Page 448: ......
Page 460: ......
Page 466: ......
Page 476: ......
Page 482: ......
Page 494: ......
Page 500: ......
Page 522: ......
Page 526: ......
Page 528: ......
Page 534: ......
Page 536: ......
Page 550: ......
Page 570: ......
Page 586: ......
Page 600: ......