Date Code 20010625
Inputs, Outputs, Timers, and Other Control Logic
7-49
SEL-311L Instruction Manual
Switch to Setting Group 4 as the Active Setting Group
When setting Group 4 is the active setting group, the reclosing relay is always disabled and
optoisolated input IN102 has no control over the reclosing relay. The text settings cannot be
changed (they are used in all setting groups), but the SEL
OGIC
control equation settings can be
changed:
SEL
OGIC
control equation settings:
79DTL = 1
(set directly to logical 1—reclosing relay
permanently “driven-to-lockout”)
DP1
= 0
(set directly to logical 0)
Text settings (remain the same for all setting groups):
DP1_1 = 79 ENABLED
(displayed when DP1 = logical 1)
DP1_0 = 79 DISABLED
(displayed when DP1 = logical 0)
Because SEL
OGIC
control equation display point setting DP1 is always at logical 0, the
corresponding text setting DP1_0 continually displays in the rotating default displays:
%*4"#-&%
Additional Rotating Default Display Example
See Figure 5.20 and accompanying text in
Section 5: Trip and Target Logic
for an example of
resetting a rotating default display with the TARGET RESET pushbutton.
Summary of Contents for SEL-311L
Page 6: ......
Page 8: ......
Page 26: ......
Page 54: ......
Page 144: ......
Page 216: ......
Page 252: ......
Page 302: ......
Page 338: ......
Page 480: ......
Page 484: ......
Page 486: ......
Page 502: ......
Page 532: ...12 28 Standard Event Reports and SER Date Code 20010625 SEL 311L Instruction Manual 4 ...
Page 552: ......
Page 554: ......
Page 574: ......
Page 576: ......
Page 596: ......
Page 602: ......
Page 628: ......
Page 656: ......
Page 662: ......
Page 664: ......
Page 688: ......
Page 700: ......
Page 716: ......
Page 722: ......
Page 734: ......