Date Code 20010625
Breaker Monitor and Metering Functions
8-19
SEL-311L Instruction Manual
Station DC Battery Voltage Dips During Circuit Breaker Closing
To generate an event report when the SEL-311L Relay closes the circuit breaker, make the
SEL
OGIC
control equation event report generation setting:
ER = / ...
In this example, output contact OUT102 is set to close:
OUT102 = CLOSE
(CLOSE is the logic output of Figure 6.1)
When output contact OUT102 closes and energizes the circuit breaker close coil, any change in
station dc battery voltage can be observed in column Vdc in the event report.
This event report generation setting (ER = / ...) might be made just as a test setting.
Generate several event reports when doing circuit breaker close testing and observe the
“signature” of the station dc battery voltage in column Vdc in the event reports.
Station DC Battery Voltage Dips Anytime
To generate an event report whenever there is a change in station dc battery voltage dip, set the
dc voltage element directly in the SEL
OGIC
control equation event report generation setting:
ER = \SV4T + ...
Timer output SV4T is an example dc voltage element from the bottom of Figure 8.10. Any time
dc voltage falls below pickup DCHIP, timer output SV4T drops out (logical 1 to logical 0
transition), creating a falling-edge condition that generates an event report.
Also, the Sequential Event Recorder (SER) report can be used to time-tag station dc battery
voltage dips (see
Sequential Events Recorder [SER] Report
in
Section 12: Standard Event
Reports and SER
).
Operation of Station DC Battery Monitor When AC Voltage Is Powering the Relay
If the SEL-311L Relay has a 125/250 Vac/Vdc supply, it can be powered by ac voltage (85 to
264 Vac) connected to the rear-panel terminals labeled POWER. When powering the relay with
ac voltage, the dc voltage elements in Figure 8.9 see the average of the sampled ac voltage
powering the relay—which is very near zero volts (as displayed in column Vdc in event reports).
Pickup settings DCLOP and DCHIP should be set off (DCLOP = OFF, DCHIP = OFF) since
they are of no real use.
If a “raw” event report is displayed (with the
EVE R
command), column Vdc will display the
sampled ac voltage waveform, rather than the average.
Summary of Contents for SEL-311L
Page 6: ......
Page 8: ......
Page 26: ......
Page 54: ......
Page 144: ......
Page 216: ......
Page 252: ......
Page 302: ......
Page 338: ......
Page 480: ......
Page 484: ......
Page 486: ......
Page 502: ......
Page 532: ...12 28 Standard Event Reports and SER Date Code 20010625 SEL 311L Instruction Manual 4 ...
Page 552: ......
Page 554: ......
Page 574: ......
Page 576: ......
Page 596: ......
Page 602: ......
Page 628: ......
Page 656: ......
Page 662: ......
Page 664: ......
Page 688: ......
Page 700: ......
Page 716: ......
Page 722: ......
Page 734: ......