8-28
Breaker Monitor and Metering Functions
Date Code 20010625
SEL-311L Instruction Manual
following settings from Table 8.3, pertinent residual ground overcurrent element settings, and
SEL
OGIC
control equation torque control setting 51GTC:
EDEM
=
THM
DMTC
=
5
GDEMP
=
1.0
51GP =
1.50
50G2P
=
2.30
51GTC
= !GDEM + GDEM * 50G2
Refer to Figure 8.15, Figure 8.16, and Figure 3.24.
Figure 8.16: Raise Pickup of Residual Ground Time-Overcurrent Element for Unbalance
Current
Residual Ground Demand Current Below Pickup GDEMP
When unbalance current I
G
is low, unbalance demand current I
G(DEM)
is below corresponding
demand pickup GDEMP = 1.00 A secondary, and Relay Word bit GDEM is deasserted to logical
0. This results in SEL
OGIC
control equation torque control setting 51GTC being in the state:
51GTC = !GDEM + GDEM * 50G2 = NOT(GDEM) + GDEM * 50G2
= NOT(logical 0) + (logical 0) * 50G2 = logical 1