8-32
Breaker Monitor and Metering Functions
Date Code 20010625
SEL-311L Instruction Manual
Maximum/Minimum Metering Updating and Storage
The SEL-311L Relay updates maximum/minimum values, if the following conditions are met:
v
SEL
OGIC
control equation setting FAULT is deasserted (= logical 0).
The factory default setting is set with time-overcurrent and distance element pickups:
FAULT = 51G + 51Q + M2P + Z2G
If there is a fault, these elements pick up and block updating of maximum/minimum
metering values. Maximum/minimum recording resumes 1 minute after FAULT deasserts.
v
The metering value is above the previous maximum or below the previous minimum for 2
cycles.
v
For voltage values, the voltage is above 13 V secondary.
v
For current values, the currents are above:
0.25 A secondary {5 A nominal}
0.05 A secondary {1 A nominal}
v
Megawatt and megavar values are subject to the above voltage and current thresholds.
The SEL-311L Relay stores maximum/minimum values to nonvolatile storage once per day (it
overwrites the previous stored value if it is exceeded). Should the relay lose control power, it
will restore the maximum/minimum values saved by the relay at 23:50 hours on the previous
day.
Summary of Contents for SEL-311L
Page 6: ......
Page 8: ......
Page 26: ......
Page 54: ......
Page 144: ......
Page 216: ......
Page 252: ......
Page 302: ......
Page 338: ......
Page 480: ......
Page 484: ......
Page 486: ......
Page 502: ......
Page 532: ...12 28 Standard Event Reports and SER Date Code 20010625 SEL 311L Instruction Manual 4 ...
Page 552: ......
Page 554: ......
Page 574: ......
Page 576: ......
Page 596: ......
Page 602: ......
Page 628: ......
Page 656: ......
Page 662: ......
Page 664: ......
Page 688: ......
Page 700: ......
Page 716: ......
Page 722: ......
Page 734: ......