S
ETTINGS
S
HEET
Page 14
OF
30
FOR THE
SEL-311L R
ELAY
(APP = 311L)
Date
R
ELAY
S
ETTINGS
(S
ERIAL
P
ORT
C
OMMAND
SET
AND
F
RONT
P
ANEL
)
Date Code 20011112
Zone 1 Extension Scheme Settings (See Figure 3.38)
(Make the following settings if preceding enable setting EZ1EXT = Y.)
Zone 1 extension delay time (0.00–16000.00 cycles)
Z1EXTD =
Zone 1 distance multiplier (1.00–4.00)
Z1EXTM =
Demand Metering Settings (See Figures 8.13 and 8.15)
(Make the following settings, whether preceding enable setting EDEM = THM or ROL.)
Time constant (5, 10, 15, 30, 60 minutes)
DMTC =
Phase pickup (OFF, 0.50–16.00 A secondary {5 A nom.};
0.10–3.20 A secondary {1 A nom.})
PDEMP =
Residual ground pickup (OFF, 0.50–16.00 A secondary {5 A nom.};
0.10–3.20 A secondary {1 A nom.})
GDEMP =
Negative-sequence pickup (OFF, 0.50–16.00 A secondary {5 A nom.};
0.10–3.20 A secondary {1 A nom.})
QDEMP =
Other Settings
Minimum trip duration time (4.00–16000.00 cycles in 0.25-cycle steps)
(see Figure 5.4)
TDURD =
Close failure time delay (OFF, 0.00–16000.00 cycles in 0.25-cycle steps)
(see Figure 6.1)
CFD =
Three-pole open time delay (0.00–60.00 cycles in 0.25-cycle steps)
(usually set for no more than a cycle; see Figure 5.5)
3POD =
Open pole option (52, 27)
OPO =
Three-pole open undervoltage (0.0–150.0 V secondary)
27PO =
Load detection phase pickup (OFF, 0.25–100.00A{5 A nom.};
0.05–20.00 A {1 A nom.}) (see Figure 5.5)
50LP =
SEL
OGIC
Control Equation Variable Timers (See Figures 7.23 and 7.24)
(Number of timer pickup/dropout settings dependent on preceding enable setting ESV = 1–16.)
SV1 Pickup Time (0.00–999999.00 cycles in 0.25-cycle steps)
SV1PU =
SV1 Dropout Time (0.00–999999.00 cycles in 0.25-cycle steps)
SV1DO =
SV2 Pickup Time (0.00–999999.00 cycles in 0.25-cycle steps)
SV2PU =
SV2 Dropout Time (0.00–999999.00 cycles in 0.25-cycle steps)
SV2DO =
SV3 Pickup Time (0.00–999999.00 cycles in 0.25-cycle steps)
SV3PU =
SV3 Dropout Time (0.00–999999.00 cycles in 0.25-cycle steps)
SV3DO =
SV4 Pickup Time (0.00–999999.00 cycles in 0.25-cycle steps)
SV4PU =
SV4 Dropout Time (0.00–999999.00 cycles in 0.25-cycle steps)
SV4DO =
SV5 Pickup Time (0.00–999999.00 cycles in 0.25-cycle steps)
SV5PU =
SV5 Dropout Time (0.00–999999.00 cycles in 0.25-cycle steps)
SV5DO =
SV6 Pickup Time (0.00–999999.00 cycles in 0.25-cycle steps)
SV6PU =
Summary of Contents for SEL-311L
Page 6: ......
Page 8: ......
Page 26: ......
Page 54: ......
Page 144: ......
Page 216: ......
Page 252: ......
Page 302: ......
Page 338: ......
Page 480: ......
Page 484: ......
Page 486: ......
Page 502: ......
Page 532: ...12 28 Standard Event Reports and SER Date Code 20010625 SEL 311L Instruction Manual 4 ...
Page 552: ......
Page 554: ......
Page 574: ......
Page 576: ......
Page 596: ......
Page 602: ......
Page 628: ......
Page 656: ......
Page 662: ......
Page 664: ......
Page 688: ......
Page 700: ......
Page 716: ......
Page 722: ......
Page 734: ......