Date Code 20010625
Line Current Differential Communications
10-13
and Serial Port Communications and Commands
SEL-311L Instruction Manual
The default settings for all serial ports are:
Baud
Rate
=
2400
Data
Bits
=
8
Parity =
N
Stop
Bits
=
1
To change the port settings, use the
SET P
command (see
Section 9: Setting the Relay
) or the
front-panel SET pushbutton (see
Section 11: Front-Panel Interface
).
P
ORT
C
ONNECTOR AND
C
OMMUNICATIONS
C
ABLES
Figure 10.4: DB-9 Connector Pinout for EIA-232 Serial Ports
IRIG-B
Refer to Figure 1.5 and Figure 2.2 through Figure 2.5. Note that demodulated IRIG-B time code
can be input into Serial Port 1 or Serial Port 2 on any of the SEL-311L Relay models. This is
easily handled by connecting Serial Port 2 of the SEL-311L Relay to an SEL-2020 with Cable
C273A (see cable diagrams that follow in this section).
Note that demodulated IRIG-B time code can be input into the connector for Serial Port 1. If
demodulated IRIG-B time code is input into this connector, it should not be input into Serial
Port 2, and vice versa.
Table 10.2: Pinout Functions for EIA-232 Serial Ports 2, 3, and F
Pin
Port 2
Port 3
Port F
1
N/C or +5 Vdc
1
N/C or +5 Vdc
1
N/C
2 RXD
RXD
RXD
3 TXD
TXD
TXD
4 +IRIG-B
N/C
N/C
5, 9
GND
GND
GND
6 -IRIG-B
N/C
N/C
7 RTS
RTS
RTS
8 CTS
CTS
CTS
1
See
EIA-232 Serial Port Jumpers
in
Section 2: Installation
.
(female chassis connector, as viewed from outside)
Summary of Contents for SEL-311L
Page 6: ......
Page 8: ......
Page 26: ......
Page 54: ......
Page 144: ......
Page 216: ......
Page 252: ......
Page 302: ......
Page 338: ......
Page 480: ......
Page 484: ......
Page 486: ......
Page 502: ......
Page 532: ...12 28 Standard Event Reports and SER Date Code 20010625 SEL 311L Instruction Manual 4 ...
Page 552: ......
Page 554: ......
Page 574: ......
Page 576: ......
Page 596: ......
Page 602: ......
Page 628: ......
Page 656: ......
Page 662: ......
Page 664: ......
Page 688: ......
Page 700: ......
Page 716: ......
Page 722: ......
Page 734: ......