Date Code 20010625
Line Current Differential Communications
10-19
and Serial Port Communications and Commands
SEL-311L Instruction Manual
4. You can use the XON/XOFF protocol to control the relay during data transmission. When
the relay receives XOFF during transmission, it pauses until it receives an XON character. If
there is no message in progress when the relay receives XOFF, it blocks transmission of any
message presented to its buffer. Messages will be accepted after the relay receives XON.
The CAN character (ASCII hex 18) aborts a pending transmission. This is useful in terminating
an unwanted transmission.
Control characters can be sent from most keyboards with the following keystrokes:
XON:
<CNTRL> Q
(hold down the Control key and press Q)
XOFF:
<CNTRL> S
(hold down the Control key and press S)
CAN:
<CNTRL> X
(hold down the Control key and press X)
SEL Distributed Port Switch Protocol (LMD)
The SEL Distributed Port Switch Protocol (LMD) permits multiple SEL relays to share a
common communications channel. The protocol is selected by setting the port setting
PROTO = LMD. See
Appendix C
for more information on SEL Distributed Port Switch
Protocol (LMD).
SEL Fast Meter Protocol
SEL Fast Meter protocol supports binary messages to transfer metering and control messages.
The protocol is described in
Appendix D
.
SEL Compressed ASCII Protocol
SEL Compressed ASCII protocol provides compressed versions of some of the relay ASCII
commands. The protocol is described in
Appendix E
.
Distributed Network Protocol (DNP) 3.00
The relay provides Distributed Network Protocol (DNP) 3.00 slave support. DNP is an optional
protocol and is described in
Appendix H
.
M
IRRORED
B
ITS
Communications
The SEL-311L Relay supports M
IRRORED
B
ITS
relay-to-relay communications on two ports
simultaneously. See
Appendix I
.
S
ERIAL
P
ORT
A
UTOMATIC
M
ESSAGES
When the serial port AUTO setting is Y, the relay sends automatic messages to indicate specific
conditions. The automatic messages are described in Table 10.5.
Summary of Contents for SEL-311L
Page 6: ......
Page 8: ......
Page 26: ......
Page 54: ......
Page 144: ......
Page 216: ......
Page 252: ......
Page 302: ......
Page 338: ......
Page 480: ......
Page 484: ......
Page 486: ......
Page 502: ......
Page 532: ...12 28 Standard Event Reports and SER Date Code 20010625 SEL 311L Instruction Manual 4 ...
Page 552: ......
Page 554: ......
Page 574: ......
Page 576: ......
Page 596: ......
Page 602: ......
Page 628: ......
Page 656: ......
Page 662: ......
Page 664: ......
Page 688: ......
Page 700: ......
Page 716: ......
Page 722: ......
Page 734: ......