10-30
Line Current Differential Communications
Date Code 20010625
and Serial Port Communications and Commands
SEL-311L Instruction Manual
There may be up to 255 records in the extended report. To limit the number of COMM records
displayed in the report to the 10 most recent records, type
COM
n
10 L <ENTER>
. To select
lines 10 through 20 of the COMM records for display in the report, type
COM
n
10 20 L
<ENTER>
. To reverse the order of the COMM records in the report, supply a range of row
numbers, with the larger number first, i.e.,
COM
n
40 10 L <ENTER>
. To display all the
COMM records that started on a particular day, supply that date as a parameter, i.e.,
COM
n
2/8/98 L <ENTER>
. To display all the COMM records that started between a range of dates,
supply both dates as parameters, i.e.,
COM
n
2/21/98 2/7/98 L <ENTER>
. Reversing the order
of the dates will reverse the order of the records in the report. To receive a summary report for a
subset of the records, use one of the above methods while omitting the L parameter.
To clear the COMM records, type
COM
n
C <ENTER>
. The prompting message “Are you sure
(Y/N) ?” is displayed. Typing
N <ENTER>
aborts the clearing operation with the message
“Canceled.” If both M
IRRORED
B
ITS
channels are enabled, omitting the channel specifier in the
clear command will cause both channels to be cleared.
CST Command
Display status data in compressed ASCII format. For details on this and other Compressed
ASCII commands see
Appendix E: Compressed ASCII Commands
.
CSU Command
Display long summary event report in compressed ASCII format. For details on this and other
Compressed ASCII commands see
Appendix E: Compressed ASCII Commands
.
DAT Command (View/Change Date)
DAT
displays the date stored by the internal calendar/clock. If the date format setting DATE_F
is set to MDY, the date is displayed as month/day/year. If the date format setting DATE_F is set
to YMD, the date is displayed as year/month/day.
To set the date, type
DAT mm/dd/yy <ENTER>
if the DATE_F setting is MDY. If the
DATE_F is set to YMD, enter
DAT yy/mm/dd <ENTER>
. To set the date to June 1, 1999,
enter when DATE_F = MDY:
=>DAT 6/1/99 <ENTER>
06/01/99
=>
You can separate the month, day, and year parameters with spaces, commas, slashes, colons, and
semicolons.
Note:
After setting date or time, allow at least 60 seconds before powering down the relay or
the new setting may be lost.
Summary of Contents for SEL-311L
Page 6: ......
Page 8: ......
Page 26: ......
Page 54: ......
Page 144: ......
Page 216: ......
Page 252: ......
Page 302: ......
Page 338: ......
Page 480: ......
Page 484: ......
Page 486: ......
Page 502: ......
Page 532: ...12 28 Standard Event Reports and SER Date Code 20010625 SEL 311L Instruction Manual 4 ...
Page 552: ......
Page 554: ......
Page 574: ......
Page 576: ......
Page 596: ......
Page 602: ......
Page 628: ......
Page 656: ......
Page 662: ......
Page 664: ......
Page 688: ......
Page 700: ......
Page 716: ......
Page 722: ......
Page 734: ......